Enviromaster CHP Скачать руководство пользователя страница 26

E-mail: [email protected]

Made in Rome, New York, USA

26

TROUBLESHOOTING PROCEDURE

 

Continued

is also equipped with a one time fuse link. Should electric 

heat temperatures rise above the auto resetting limit switch, 

a non-resetting, one time fuse link will open and the heater 

will remain off.

The following current values apply when the unit is connected 

to a 230V power supply. These values include fan motor 

current. If the supply power is different, this will in turn affect 

the amp draw of the heater.

5kw = 22.3 amps,    4kw = 18 amps,     3kw = 13.5 amps.

Optional Heat pump with Electric Heat

Heat  pump  units  with  electric  heat  utilize  four  to  six 

interconnecting, 

low Volt

  wires  depending  control  setup 

and/or thermostat selected. Refer to the low Volt interconnect 

section and figures 1, 2 and 3 for your particular unit. 

As 

of 12/01/04, a 24V transformer located in the indoor 

air handler

 provides low Volt control power to both the air 

handler and condenser. With high Volt power supplied to the 

condenser, 24V can be measured across the red (R) and 

brown (C) wires at all times.

Cooling:

The air handler will cycle the condenser on and off through 

the yellow (Y) wire. To check for a condenser signal, select 

cooling mode on the indoor unit or thermostat and place 

the set-point temperature below room temperature. Then, 

with a voltmeter check for 24 Volts across the yellow (Y) 

and brown (C) wires. If no signal is found then re-check 

all wiring connections to ensure that they match the low 

volt  interconnect  diagram.  Check  the  output  of  the  24V 

transformer (located in the air handler as of 12/01/04) to 

ensure that the control voltage is present.

EMI heat pump systems utilize a reversing valve is that is 

energized in the cooling mode. The reversing-valve signal 

is provided through the orange (O) low Volt wire of the air 

handler or thermostat. It should remain energized constantly 

as long as the indoor unit or thermostat remains in cooling 

mode. To  check  for  24V  reversing  valve  voltage,  at  the 

outdoor unit, place a voltmeter across the brown (C) and 

orange (O) wires while in the cooling mode. 

Heating:

Heat pump units can accommodate two-stage heating when 

an optional electric strip heater is present along with a heat 

pump condenser. The first stage being the compressor and 

the second is electric heat. The air handler or wall thermostat 

will cycle the condenser through the yellow (Y) wire as it does 

in cooling however the reversing valve will not be energized. 

To check for a condenser signal, place the indoor unit or wall 

thermostat in heating. Next place the set-point temperature 

one degree above room temperature to call the first stage 

of heating. Then, with a voltmeter check for 24 Volts across 

the yellow (Y) and brown (C) wires at the condenser. The 

electric heat should be off at this point. Select a set-point 

temperature  that  is  more  than  two  degrees  above  the 

room temperature to call for the second stage of heating. 

The  electric  heat  should  energize  along  with  the  24V 

compressor signal between “Y” and “C”. Check to see that 

the amp draw corresponds with the electric heat rating. 

The  following  current  values  apply  when  the  unit  is 

connected to a 230V power supply. These values include 

indoor fan motor current. If the supply power is different, 

this will affect the amp draw of the heater.

5kw = 22.3 amps,    4kw = 18 amps,     3kw = 13.5 amps.

Units with electric heat utilize a control relay located on the 

circuit board in the control box. As a safety feature, an auto 

resetting limit switch located on the heater end plate or on 

the heater assembly will interrupt power to the heater should 

an over-heat condition occur. Each electric heat assembly 

is also equipped with a one time fuse link. Should electric 

heat temperatures rise above the auto resetting limit switch, 

a non-resetting, one time fuse link will open and the heater 

will remain off.

Units With Condensation Pumps

EMI Air Handlers are available with an optional condensate 

pump. Condensate pumps are recommended when it is not 

possible to gravity drain the condensation from the indoor 

unit. Depending on the pump manufacture the maximum 

lift for the pump will vary. Consult the pump instructions for 

the maximum lift for the particular pump being used.

Condensation generated by the evaporator will collect in the 

pumps’ reservoir. When the water level is high enough, a 

float switch will close and energize the pump motor clearing 

the water from the reservoir. Should for any reason the 

water exceed the maximum preset level, a safety switch will 

open, there by interrupting the (Y) signal to the condenser. 

This  will  prevent  the  evaporator  from  generating  more 

condensation and spilling out of the unit.

Error Codes

Should for some reason one of the two temperature 

sensors become disconnected or fail, an error code 

will appear in the display. The control will not operate 

properly until the sensor is working.

E1

  –  Coil  Sensor  malfunction  or  disconnected.  Check 

location 

J1

 on thermostat board.

E2

 – Room Air Sensor malfunction or disconnected. Check 

location 

J2

 on thermostat board.

Содержание CHP

Страница 1: ...NCE MANUAL EMI DUCTLESS SPLIT SYSTEM AIR HANDLERS FLOOR MODEL AIR HANDLER FCP FHP WALL MOUNTED AIR HANDLER WCP WHP CEILING MOUNTED AIR HANDLER CHP An ISO 9001 2000 Certi ed Company Enviromaster Intern...

Страница 2: ...lting in re electrical shock property damage personal injury or death TO THE INSTALLER 1 Retain this manual and warranty for future refer ence 2 Before leaving the premises review this manual to be su...

Страница 3: ...ring 18 awg required High voltage power supply wiring Mounting fasteners screws wall anchors etc Chilled water condensate and refrigerant piping Refrigerant for interconnect charge Hot water piping Fl...

Страница 4: ...unit The cabinet service panels must be able to be removed without obstruction FCP FHP CCP CHP units can be equipped with hot water coil Unit mount control panel standard on FHP FCP and WHP WCP optio...

Страница 5: ...l surfaces LOW VOLT INTERCONNECT WIRING FOR UNIT MOUNTED CONTROLS In addition to the Y and C connections required for cooling heat pumps require a reversing valve control wire O orange that is energiz...

Страница 6: ...Heat pump operation requires the connection of the O orange terminal from the outdoor unit to the thermostat The reversing valve is energized in the cooling mode for EMI models SHC heat pump condenser...

Страница 7: ...according to the table below Figure 4 FHP FCP to gain access to the relay board rst remove the return air grill from the bottom front of the unit The relay board is located in the control section Set...

Страница 8: ...for mounting the unit for optimum air circulation 3 Locate the indoor and outdoor units as close together as possible See outdoor unit requirements UNIT MOUNTING The FHP FCP is designed to sit direct...

Страница 9: ...FRIGERANT PIPING The FHP is equipped with a Flo Rater Piston Expan sion Device Connections are male are type are nuts not included The suction line large must be insulated the entire length with close...

Страница 10: ...DIMENSIONS AND SPECIFICATIONS NOTE Due to ongoing development programs design and speci cations may change without notice FCP PIPING SPECIFICATIONS Model Chilled Water Line Size Supply Return Drain H...

Страница 11: ...om FHP Electric Heat Speci cations table 36 requires piston kit 550 121 see pg 5 FCP FHP ELECTRICAL HEAT SPECIFICATIONS Model Voltage KW Heater Amps Total Amps Min Circuit Amps Max Fuse Amps 9 12 15 2...

Страница 12: ...torized Damper and Power Assisted Fresh Air 2 Fan Type Wall Box Dimensions 14 from nished oor level x 17 wide x 8 deep Model Air Handler Condenser Btuh Factory Installed Field Changeover Part Piston O...

Страница 13: ...Use the cardboard template provided with unit packing to test t the unit before installation 1 The CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Using...

Страница 14: ...3 4 Flare nuts not included CHP WITH ELECTRIC HEAT OPTIONS Model Voltage KW Htr Amps Total Amps Min Cir Amps Max Fuse 12 208 230 3 13 1 13 7 17 1 20 18 24 208 230 5 21 7 22 8 28 6 30 CHP ELECTRICAL SP...

Страница 15: ...rom unit Determine if the cabinet front can be removed with out obstruction WALL MOUNTED AIR HANDLER WCP WHP NOTE Please refer to the Common section in the front of this manual for more detailes on Co...

Страница 16: ...Factory Installed Field Replacement Part Piston Ori ce Piston Ori ce Size Part Piston Ori ce Piston Ori ce Size WHP12 9 000 240 4064 044 240 727 041 12 000 NO CHANGE WHP18 15 000 240 4111 053 240 101...

Страница 17: ...21 7 22 3 27 9 30 36 230 5 21 7 22 3 27 9 30 WCP CAPACITIES Model Nominal Capacaties Total Capacity Sensible Capacity Fluid Temp Fluid Flow PD Ft H2 0 09 12 9 000 7 375 6 732 45 1 0 8 10 801 8 272 45...

Страница 18: ...is designed to optimize system performance and protect the refrigeration system from unwanted short cycling and evaporator freeze ups Operation of the unit can be made by either the keypad on the uni...

Страница 19: ...ton Select Cool mode via the Mode button The room temperature will be displayed Then by depressing either the Up or Down arrow once the setpoint temperature will appear The setpoint temperature can th...

Страница 20: ...tpoint temperature will appear The setpoint temperature can then be changed with each successive press of the Up or Down arrow or by holding the button in Placethesetpointtemperatureatadesiredroomtemp...

Страница 21: ...quipped with an auto on fan switch When this switch is placed in the on position the indoor fan will run continuous When the switch is in the auto position the indoor fan will cycle with the call for...

Страница 22: ...system or from abnormally cold air from the evaporator coil Should the freeze sensor activate the indoor fan will switch off to eliminate the source of cold fresh air and also the outdoor condensing...

Страница 23: ...l Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air WB Outdoor Section Entering A...

Страница 24: ...ailure to do so could result in physical injury and or electrical shock When trouble shooting the indoor unit please refer to the wiring diagram that is supplied with the equipment It is located eithe...

Страница 25: ...mote thermostat connection A 24V transformer located in the indoor air handler unit as of 12 01 04 provides low Volt control power to both the indoor air handler and outdoor condenser The 24V power su...

Страница 26: ...eversing valve will not be energized To check for a condenser signal place the indoor unit or wall thermostat in heating Next place the set point temperature one degree above room temperature to call...

Страница 27: ...ce all circuit boards including the unit keypad Do not attempt to trouble shoot the individual circuit boards Q The display tends to icker at times Is this normal A A small amount of ickering of the d...

Страница 28: ...or application by others Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs nee...

Отзывы: