Enviromaster CHP Скачать руководство пользователя страница 22

E-mail: [email protected]

Made in Rome, New York, USA

22

 

After connecting the thermostat to the unit place the 

system  switch  in 

cool 

mode. Adjust  the  set-point  tem-

perature  below  the  room  temperature. The  compressor 

and fan motors will start and cooling will begin. For chilled 

water systems, the coldwater valve will open allowing the 

flow of water. Place the set-point temperature above the 

room temperature. The outdoor condenser will stop (or CW 

valve will close) while the indoor fan will remain on for an 

additional sixty seconds.

ELECTRIC HEAT OPERATION

 

Place  the  thermostat  system  switch  in 

heat  mode

Adjust the set-point temperature above the room tempera-

ture. The electric heat will energize along with the indoor 

fan motor. Heating will continue so long as the set-point 

remains above room temperature. Next place the set-point 

temperature below room temperature. The electric heater 

will switch off and the indoor fan will remain on for an ad-

ditional sixty seconds.

HYDRONIC HEAT OPERATION

 (Optional On CHP And FHP Units)

 

An optional hydronic heat package may be selected 

in lieu of electric heat. Heating operation is essentially the 

same as that of units with electric heat. With the thermostat 

system switch

 set to 

heat

 and the set-point temperature 

above room temperature, the hydronic valve will open al-

lowing water to flow through the coil. The indoor fan will 

also switch on and warm air will flow from the unit. Heating 

will continue so long as the set-point remains above room 

temperature. Place the set-point temperature below room 

temperature.  The  hydronic  valve  will  close  and  indoor 

fan  will  switch  off  after  the  sixty-second  purge  time  has 

elapsed.

 

Units with an optional hydronic heat coil or chilled water 

coil are also equipped with a freeze protection thermostat. 

The  freeze  protection  thermostat  is  designed  to  protect 

the hydronic coil or chilled water coil from freeze up due 

to abnormally cold fresh air from the fresh air system or 

from abnormally cold air from the evaporator coil. Should 

the freeze sensor activate, the indoor fan will switch off to 

eliminate the source of cold fresh air, and also the outdoor 

condensing  unit  will  be  switched  off  eliminating  cold  air 

COMMON TO ALL AIR HANDLERS - SEQUENCE OF OPERATION

 

Continued

from the refrigeration system. For units with a hydronic hot 

water valve installed, the valve will be energized allowing 

warm water to flow and assist in the defrost process. The 

system will remain in this state until the freeze condition is 

satisfied where-by the freeze thermostat will reset.

HEAT PUMP

(Cooling Mode)

 

Cooling  operation  in  a  heat  pump  unit  is  described 

in “Cooling operation” above. Heatpump condensers are 

equipped with a reversing valve that is energized for cooling 

and de-energized for heatpump mode.

OPTIONAL HEAT PUMP WITH 

ELECTRIC HEAT 

(2-Stage Heating)

 

The electronic circuit board of the indoor unit also has 

an anti-short cycle timer (ASCT) feature designed to protect 

the compressor from short cycling. The ASCT is activated 

immediately following the off cycle of the outdoor unit. Once 

the  room  temperature  is  satisfied  and  the  outdoor  unit 

switches off, the ASCT will not allow the outdoor to restart 

unit a three-minute time period has elapsed. 

 

After connecting the thermostat to the unit place the 

system switch in 

heat

 mode. Adjust the set-point tempera-

ture  above  the  room  temperature. The  compressor  and 

fan motors will start and heating will begin. Depending on 

the  thermostat  selected,  electric  heat  will  also  energize 

when  the  deviation  between  room  temperature  and  set 

point temperature is greater than two degrees. (See the 

thermostat owner’s manual for this feature) Place the set-

point temperature below the room temperature. The outdoor 

condenser and electric heat will stop while the indoor fan 

will remain on for an additional sixty seconds.

After starting the unit, complete the 

Test Unit Performance Data

 

sheet on page 23. 

Save this information for future servicing. In the event there is a problem with the unit. 

 Perform the test again (if possible) and have both sets of data ready when 

calling for assistance.  

Содержание CHP

Страница 1: ...NCE MANUAL EMI DUCTLESS SPLIT SYSTEM AIR HANDLERS FLOOR MODEL AIR HANDLER FCP FHP WALL MOUNTED AIR HANDLER WCP WHP CEILING MOUNTED AIR HANDLER CHP An ISO 9001 2000 Certi ed Company Enviromaster Intern...

Страница 2: ...lting in re electrical shock property damage personal injury or death TO THE INSTALLER 1 Retain this manual and warranty for future refer ence 2 Before leaving the premises review this manual to be su...

Страница 3: ...ring 18 awg required High voltage power supply wiring Mounting fasteners screws wall anchors etc Chilled water condensate and refrigerant piping Refrigerant for interconnect charge Hot water piping Fl...

Страница 4: ...unit The cabinet service panels must be able to be removed without obstruction FCP FHP CCP CHP units can be equipped with hot water coil Unit mount control panel standard on FHP FCP and WHP WCP optio...

Страница 5: ...l surfaces LOW VOLT INTERCONNECT WIRING FOR UNIT MOUNTED CONTROLS In addition to the Y and C connections required for cooling heat pumps require a reversing valve control wire O orange that is energiz...

Страница 6: ...Heat pump operation requires the connection of the O orange terminal from the outdoor unit to the thermostat The reversing valve is energized in the cooling mode for EMI models SHC heat pump condenser...

Страница 7: ...according to the table below Figure 4 FHP FCP to gain access to the relay board rst remove the return air grill from the bottom front of the unit The relay board is located in the control section Set...

Страница 8: ...for mounting the unit for optimum air circulation 3 Locate the indoor and outdoor units as close together as possible See outdoor unit requirements UNIT MOUNTING The FHP FCP is designed to sit direct...

Страница 9: ...FRIGERANT PIPING The FHP is equipped with a Flo Rater Piston Expan sion Device Connections are male are type are nuts not included The suction line large must be insulated the entire length with close...

Страница 10: ...DIMENSIONS AND SPECIFICATIONS NOTE Due to ongoing development programs design and speci cations may change without notice FCP PIPING SPECIFICATIONS Model Chilled Water Line Size Supply Return Drain H...

Страница 11: ...om FHP Electric Heat Speci cations table 36 requires piston kit 550 121 see pg 5 FCP FHP ELECTRICAL HEAT SPECIFICATIONS Model Voltage KW Heater Amps Total Amps Min Circuit Amps Max Fuse Amps 9 12 15 2...

Страница 12: ...torized Damper and Power Assisted Fresh Air 2 Fan Type Wall Box Dimensions 14 from nished oor level x 17 wide x 8 deep Model Air Handler Condenser Btuh Factory Installed Field Changeover Part Piston O...

Страница 13: ...Use the cardboard template provided with unit packing to test t the unit before installation 1 The CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Using...

Страница 14: ...3 4 Flare nuts not included CHP WITH ELECTRIC HEAT OPTIONS Model Voltage KW Htr Amps Total Amps Min Cir Amps Max Fuse 12 208 230 3 13 1 13 7 17 1 20 18 24 208 230 5 21 7 22 8 28 6 30 CHP ELECTRICAL SP...

Страница 15: ...rom unit Determine if the cabinet front can be removed with out obstruction WALL MOUNTED AIR HANDLER WCP WHP NOTE Please refer to the Common section in the front of this manual for more detailes on Co...

Страница 16: ...Factory Installed Field Replacement Part Piston Ori ce Piston Ori ce Size Part Piston Ori ce Piston Ori ce Size WHP12 9 000 240 4064 044 240 727 041 12 000 NO CHANGE WHP18 15 000 240 4111 053 240 101...

Страница 17: ...21 7 22 3 27 9 30 36 230 5 21 7 22 3 27 9 30 WCP CAPACITIES Model Nominal Capacaties Total Capacity Sensible Capacity Fluid Temp Fluid Flow PD Ft H2 0 09 12 9 000 7 375 6 732 45 1 0 8 10 801 8 272 45...

Страница 18: ...is designed to optimize system performance and protect the refrigeration system from unwanted short cycling and evaporator freeze ups Operation of the unit can be made by either the keypad on the uni...

Страница 19: ...ton Select Cool mode via the Mode button The room temperature will be displayed Then by depressing either the Up or Down arrow once the setpoint temperature will appear The setpoint temperature can th...

Страница 20: ...tpoint temperature will appear The setpoint temperature can then be changed with each successive press of the Up or Down arrow or by holding the button in Placethesetpointtemperatureatadesiredroomtemp...

Страница 21: ...quipped with an auto on fan switch When this switch is placed in the on position the indoor fan will run continuous When the switch is in the auto position the indoor fan will cycle with the call for...

Страница 22: ...system or from abnormally cold air from the evaporator coil Should the freeze sensor activate the indoor fan will switch off to eliminate the source of cold fresh air and also the outdoor condensing...

Страница 23: ...l Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air WB Outdoor Section Entering A...

Страница 24: ...ailure to do so could result in physical injury and or electrical shock When trouble shooting the indoor unit please refer to the wiring diagram that is supplied with the equipment It is located eithe...

Страница 25: ...mote thermostat connection A 24V transformer located in the indoor air handler unit as of 12 01 04 provides low Volt control power to both the indoor air handler and outdoor condenser The 24V power su...

Страница 26: ...eversing valve will not be energized To check for a condenser signal place the indoor unit or wall thermostat in heating Next place the set point temperature one degree above room temperature to call...

Страница 27: ...ce all circuit boards including the unit keypad Do not attempt to trouble shoot the individual circuit boards Q The display tends to icker at times Is this normal A A small amount of ickering of the d...

Страница 28: ...or application by others Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs nee...

Отзывы: