Installation
C
LEARANCES
TO
C
OMBUSTIBLES
:
This unit can be installed on a combustible floor when installed with the optional hearth pad part EF5-103
(for example linoleum, hardwood flooring). If this unit is to be installed onto a carpeted surface, a hearth
pad must be used for stability.
A
LCOVE
C
LEARANCES
:
This unit may be installed in an alcove. Maintain
these clearances to combustibles.
Minimum Alcove width
36 inches (91 cm)
Minimum Alcove height
48 inches (122 cm)
Maximum Alcove depth
48 inches (122 cm)
Install vent at clearances specified by
the vent manufacturer.
Side
W
all
Back Wall
Adjacent
Wall
7
7
/
8
"
(20cm)
4"
(10cm)
4" (10cm)
48"
(122cm)
48"
(122cm)
48"
(122cm)
These dimensions are minimum clearances
but it is recommended that you ensure
sufficient room for serving, routine cleaning
and maintenance.
Side wall to unit 6 inches (15 cm)
Back wall to unit 3 inches (7.5 cm)
Corner to unit
3 inches (7.5 cm)
Figure 4: EF5 Clearance to Combustibles.
Figure 5: EF5 Minimum Alcove Size.
8