13
�� �
���� ����
���� �������
���� �������
�������� ���� �������
����������� ���
1. Place the appliance 15” (37.5 cm) away from the wall. If the stove is to be set on a hearth pad, set
the unit on it.
2. Locate the center of the exhaust pipe on the stove. Extend that line to the wall. Once you have located
the center point on the wall, refer to pellet vent manufacturer installation instructions for correct hole
size and clearance to combustibles.
3. Install the wall thimble as per the instructions written on the thimble. Maintain an effective vapour
barrier in accordance with local building codes.
4. Install a length of vent pipe into the wall thimble. Try not to have joints inside the thimble. The pipe
should install easily into the thimble.
5. Connect the exhaust vent pipe to the exhaust pipe on the stove. Seal the connection with high
temperature silicone.
6. Install the fresh air intake (see
O
UTSIDE
F
RESH
A
IR
C
ONNECTION
)
.
7. Push the stove straight back, leaving a minimum of 4” (10 cm) clearance from the back of the stove
to the wall. Seal the vent pipe to the thimble with high temperature silicone.
8. The pipe must extend at least 12” (30 cm) away from the building. If necessary, bring another
length of pipe to the outside of the home to connect to the first section. Do not forget to place high
temperature silicone around the pipe that passes through the thimble.
9. Install a vertical pipe, or if all requirements for direct venting are met, install vent termination.The
stainless steel cap termination manufactured by the vent manufacturer is recommended. However,
when the vent terminates several feet above ground level and there are no trees, plants, etc. within
several feet, a 45° elbow can be used as termination. The elbow must be turned down to prevent
rain from entering.
NOTE:
• It is recommended that horizontal through wall installations have 3 to 5 feet (91 to 152 cm) of vertical
pipe in the system to help naturally draft the unit in the event of extreme weather or a power outage.
Figure 13: Straight through wall Installation.
• Some horizontal through wall installations
may require a “T” and 3 to 5 feet (91 to 152
cm) of vertical pipe outside the building to
help draft the unit. This may be required if
a proper burn cannot be maintained, after
the stove has been tested and the airflow
set. This is due to the back pressure in
the exhaust caused by airflow around the
structure.
• Follow vent manufacturer guidelines for
installation of venting. High temp Sealent
must be used when connecting vent pipe
to the unit’s starter pipe. Improper seals
at the vent joints may cause combustion
by-products to leak into the room where
installed -
seal as required.
Installation