Figure 23. Combustible Mantel Clearances for Fascia or
Insets.
Initial Installation
QUALIFIED INSTALLERS ONLY
16
A shelf may be installed above the unit. We
recommend that no heat sensitive items or
components be placed on the shelf (see
Figure 22).
m
anteL
c
LeaRances
:
It is not necessary to install a mantel, but if one is desired it is important to follow the guidelines.
Note:
Louvers have different mantel clearances than when fascia or insets are installed.
Table 3: Mantel clearances.
Louvers Only
Fascia or Insets
Top of unit to horizontal framing
3” (7.6 cm)
3” (7.6 cm)
Top of unit to bottom of 3” (7.6 cm) mantel
12” (30.5 cm)
Top of unit to bottom of 3½” (8.9 cm) mantel
8” (20.3 cm
Top of unit to bottom of 10” (254 mm) mantel
10” (25.4 cm
14” (35.6 cm)
Top of unit to bottom of ¾” (19 mm) facing board
6” (15.2 cm)
6” (15.2 cm)
3"
(76mm)
Top of unit
Combustible
front face
Combustible board
Figure 22. Combustible Shelf Clearance.
Figure 21. Raised Fireplace with no Hearth
Even though the DV36 can be installed at floor
level without a hearth, there are a few options
with raised fireplaces: raised with a floor level
hearth (Figures 19), raised with a raised hearth
(Figures 20), or raised with no hearth (Figures 21).
If the fireplace is raised, it cannot be placed within
37 inches (1.04 m) of the ceiling. When installing
a raised fireplace, it is imperative that the support
stand is strong enough to hold the weight of the
fireplace and venting.
3"
(76mm)
12"
(305mm)
6"
(152mm)
14"
(356mm)
Top of unit
3” (76mm) mantle
10" (254mm) mantle
Combustible front face
3
/
4
" (19mm) facing board