5. Electrical connection
The cable length between power supply and transmitter / receiver system is a maximum of 200 m.
A double insulated shielded cable with a minimum cross section of 0.75 mm² is recommended. From a cable
length of 100 m, the cable cross-section must be increased to 1 mm².
The transmitter / receiver system has an EMV cable gland. This serves for laying a cable shield. The shield
should only be placed on the connector in the transmitter unit is additionally fastened with the existing
screws. This will ensure that the contacts will not disconnect even on vibrated places. The electrical
connection of the transmitter / receiver system is as shown in Figures 3 and 4:
L
H 0.25 s 5 s
P1
P2
LED 1
LED 2
S1 S2
5
4
3
2 1
Fig. 4: Electrical connection transmitter
2
1
Fig. 3: Electrical connection receiver
5.2 Electrical connection transmitter
1
Uin +24 V
2
Uin 0 V
5.1 Electrical connection receiver
1
Uin +24 V
2
Uin 0 V
3
Relay contact NO (make contact)
4
Relay contact COM
5
Relay contact NC (break contact)