Power Supply
6
3
Power Supply
FIGURE 3-1
Mains Supply Connections
FIGURE 3-2
WARNING
Isolate mains supply before connecting.
Fused Terminal Block
Earth Point
Pre-Wired 24V to Internal Devices
Backup Battery Connections for 2x
Sealed Lead Acid Batteries
(Connected in Series - See Section 4)
Output Voltage Adjustment
SYSTEM VOLTAGE 27.6VDC
Always test the output voltage.
Only adjust if required.
Fuse Holder
Mains Supply Cable from
Fused Spur
1.5mm² Twin Earth
LIVE
- BROWN
NEUTRAL
- BLUE
EARTH
- GREEN/YELLOW
Sheath