Quick Start Guide
APPENDIX 2
LBS-751 Control
9
www.Entec-USA.com
Modbus User-Defined Assignment Map
Boolean Points
Status Bits
Source Location
02h Read
03h Read
Tag
Word Map
Bit
Coil
User Table
Address
Bit
Breaker Closed (52A)
IN302
Row 18
6
150
MOD_040
165
6
Breaker Open (52B)
IN303
Row 18
5
149
MOD_040
165
5
Handle Lock (69)
IN301
Row 18
7
151
MOD_040
165
7
Diagnostic Alarm
T03_LED
Row 38
3
307
MOD_044
169
3
Battery Fail
T04_LED
Row 38
2
306
MOD_044
169
2
AC Power Fail
T05_LED
Row 38
1
305
MOD_044
169
1
Polarity:
Logic 1 = True Condition