393930-2 Rev 0: 01.04.2020
23 |
P a g e
4.8.3
Air quality menus
Fan speed setting at high humidity limit Range MIN, NORM, MAX; default
MAX
High humidity level when to increase fan speed Off, 40%RH to 95%RH;
default 60%RH
Off means function disabled
Max time to run fan at the high level Range Off, 1 min to 120 min; default Off
Off means no time limit
Settings for handling the air quality
Sensor control mode. Humidity and CO
2
. Range Off, Humidity, Hu CO
2
Default Hu CO
2
Fan speed setting at low humidity limit Range MIN, NORM, MAX; default MIN
Low humidity level when to reduce fan speed Off, 20%RH to 50%RH; default
40%RH
Off means function disabled
4.8.4
Defrosting menu
Defrost is done 6 min every hour by stopping supply fan and air heater.
Exhaust fan set 30% and rotor at normal speed. Condition to start defrosting
are the 3 modes.
Mode 1 at -20°C, Mode 2 at -15°C, Mode 3 at -10°C
Select defrost mode
Range Off, Mode 1, Mode 2, Mode 3