393930-2 Rev 0: 01.04.2020
29 |
P a g e
Configure if the tacho signal in the extract fan is connected Range On, Off;
default On
Configure if the tacho signal in the rotor heat exchanger is connected
Range On, Off; default Off
User code sets if the user can stop the unit. Default the user cannot stop the
unit = No OffKey.
Range No Offkey, Open; default No OffKey
5.1.1
Manual mode operation
Set the air handling unit in manual mode for trouble shooting
purposes
The relay output and analogue output is activated
Select manual mode
Range Off, Supply air, Exhaust air, Heating, Rotor; default Off
Analogue output value for capacity Range 0% .. 100%; default 50%
Fan speed during testing
Range MIN, NORM, MAX; default NORM
5.1.2
Data views
Values from the controller