5
exceed 3.5 mA.
●
CAUTION (For permanent connection only)
: HIGH LEAKAGE CURRENT, Earth connection
essential before connection supply
●
WARNING
: Intend for installation in a controlled environment.
●
CAUTION
: Do not dispose of batteries in a fire, the battery may explode.
●
CAUTION
: Do not open or mutilate the battery, released electrolyte is harmful to the skin and
eyes.
●
CAUTION
: A battery can present a risk of electric shock and high short circuit current.
The following precaution should be observed when working on batteries
A. Remove watches, rings or other metal objects.
B. Use only tools with insulated handles.
C. Wear rubber gloves and boots.
D. Do not lay tools or metal parts on top of batteries.
E. Disconnect charging source prior to connecting or disconnecting battery terminals.
To reduce the risk of electric shock, disconnect the UPS from the mains supply before installing a
computer interface signal cable. Reconnect the powers cord only after signaling interconnections
have been made.
Servicing of batteries should be performed or supervised by personnel knowledge of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
●
CAUTION
: When replacing batteries, replace with the same type and number of batteries:
One Sealed lead acid battery, rated 12 V, 9 AH max.
●
CAUTION
: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line
cord.
●
CAUTION (FOR 1000-3000VA HV Only)
: To reduce the risk of fire. Connect only to a circuit
provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the
National Electric Code, ANSI/NFPA 70”.
●
CAUTION (FOR 3000VA with I/P Terminal Block Only)
: To reduce the risk of fire. Connect
only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in
Содержание Evo UPS 1000VA
Страница 1: ...1 U P S 1000VA 3000VA USER S MANUAL 2011 11 v 1 0 ...
Страница 17: ...17 5 2 Rear panel view 1KVA REAR PANEL ...
Страница 18: ...18 2K 3KVA REAR PANEL ...
Страница 19: ...19 RM 2U 1KVA Rear Panel ...
Страница 20: ...20 RM 2U 2K 3KVA Rear Panel ...
Страница 24: ...24 6 Output Ac Fail Output 8 Output Low Battery Output 9 Output 12 VDC Power Caution Max rated values 12Vdc ...