![Enplus Evo UPS 1000VA Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/enplus/evo-ups-1000va/evo-ups-1000va_user-manual_2414039029.webp)
29
BACKUP TIME= xx min Shows Estimated Backup time in minutes
BAT CHARG= xx%
Shows approximate percentage of Battery capacity
TEMPERATURE= xxC
Shows approximate ambient temperature
BAT PACK NUM= x
Shows External Battery Pack Number
RATING = xxxxVA
Shows UPS Rating
CPU VERSION xx.x
Shows CPU Version
UPS configurations
Various settings that have been chosen are shown in the UPS setting display.
To enter configuration mode, press the button for one second. The first configuration
parameter will be shown on the LCD display.
Press the button to scroll through the parameters.
Press the button to select the parameter.
Press the button to scroll through the options for the selected parameter; Press
the button to select the option.
You may be prompted to save the selection, if so press the button to either confirm or save
your selection. Other options are saved and started automatically. See the table below for further
details.
If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the
configuration mode and return to normal mode displaying Line mode.
Caution!
The factory default settings do not necessarily have to be changed, although you are
free to tailor the UPS to your specific needs.
Settings
LCD
display
Explanation
Selection
Factory
default
Output
Volt.Setting
O/P V
Setting
Select Nominal Voltage
208/220/230/240 V
230V
100/110/115/120/127 V 120V
Input/Frequency
I/P F
Setting
Select input frequency
range when UPS goes
into free run mode
±2%
±5%
±7%
±5%
Input/Bypass
Voltage
I/P Bypass
Set
Select Input Voltage
range when bypass is
available
±10%
+10/-15%
+15/-20%
+10/-15
%
Free Run Mode
Free Run
Set
Select if UPS can run in
Free run mode
(unsynchronized)
ON/OFF
ON
Bypass
Enable/Disable at
Free run mode
Bypass
disable
If Enable is chosen, the
UPS can go to bypass
when unsynchronized.
Disable/Enable
Disable
Содержание Evo UPS 1000VA
Страница 1: ...1 U P S 1000VA 3000VA USER S MANUAL 2011 11 v 1 0 ...
Страница 17: ...17 5 2 Rear panel view 1KVA REAR PANEL ...
Страница 18: ...18 2K 3KVA REAR PANEL ...
Страница 19: ...19 RM 2U 1KVA Rear Panel ...
Страница 20: ...20 RM 2U 2K 3KVA Rear Panel ...
Страница 24: ...24 6 Output Ac Fail Output 8 Output Low Battery Output 9 Output 12 VDC Power Caution Max rated values 12Vdc ...