background image

      Verify System Configuration 

While still connected to the IQ Envoy with Installer Toolkit, check the Over-

view screen for the following: 
A )   Confirm that the expected number of devices are detected and communi-

cating.

B )  Check that the new profile is set on all the devices. Setting the profile 

may take up to 5 minutes for a typical system.

C )  Tap the 

Meters

 button. 

D )  Tap 

Production Meter

 and follow the on-screen instructions to enable 

the Production Meter.

E )   If you installed consumption metering CT(s), tap 

Consumption Meter

 

and follow the on-screen instructions to enable the Consumption 

Meter.

F )   Return to the 

Overview

 screen and verify the meter reading(s).

If you used Installer Toolkit to detect devices, the Power Production LED   

lights solid green when all 

expected

 microinverters are producing power. 

If you did not use Installer Toolkit, it lights solid green if all 

communicating

 

microinverters are producing power. It flashes green when devices are 

upgrading. Check Installer Toolkit for production status details. If the 

Power Production LED remains solid amber, see 

Troubleshooting 

 

c

.

7

INSTALLATION — Part 2

You must complete Installation Part 2 after installing the Enphase IQ 

Microinverters.

      Detect Devices

A )  Turn on the DG breaker(s).
B )  Unlock and open the Three-Phase NPR cabinet.
C )  Use one of the following methods to detect devices (Enphase IQ Microin-

verters and/or Enphase batteries):

Method A:  Provision devices with Installer Toolkit

Use the Installer Toolkit mobile app to configure the IQ Envoy with the 

serial numbers of the installed devices.
A )  Launch the Installer Toolkit app and tap 

View Systems.

B )  Select the system you are working with, or tap 

[+]

 to add a system.

C )  Connect to the IQ Envoy with your mobile device (smart phone or tablet). 

The AP Mode LED 

 lights solid green when the network is available. 

• 

On the Envoy, if the AP Mode LED is not lit, press the 

AP Mode

 button. 

• 

On your mobile device, go to Settings and join the Wi-Fi network 

“Envoy_nnnnnn” (where “nnnnnn” equals the final six digits of the IQ 

Envoy serial number).

D )  If the serial number for the Envoy you are installing is not displayed on 

the System Overview screen, tap the 

[+]

 next to the word “Envoys”. When 

the app displays the serial number of the Envoy, tap it to add it to the 

system.

E )  Following the on-screen instructions to create the arrays and scan the 

serial numbers from the installation map.

F )  Tap the 

Connect

 button. This provisions the scanned devices on the 

Envoy.

G )  When prompted, confirm the number of devices that you installed.
H )  If your system is in Hawaii or in a region that does not use the 

Factory- 

Installed Grid Profile

, select and apply a grid profile to the devices.

The Device Communications LED

 lights solid green if all provisioned 

devices are communicating or solid amber if any devices are not communi-

cating.

Method B: Discover devices with Installer Toolkit

Use the Installer Toolkit mobile app to set the number of devices the IQ 

Envoy should search for on the power line.
A )  Connect to the IQ Envoy with your mobile device (smart phone or 

tablet). The AP Mode LED 

 lights solid green when the network is 

available. 

• 

On the Envoy, if the AP Mode LED is not lit, press the AP Mode but-

ton. 

• 

On your mobile device, go to Settings and join the Wi-Fi network 

“Envoy_nnnnnn” (where “nnnnnn” equals the final six digits of the IQ 

Envoy serial number).

B )  Launch Installer Toolkit and tap 

Connect to an Envoy.

C )  When prompted, enter the number of devices that you installed.
D )  If your system is in Hawaii or in region that does not use the 

Factory- 

Installed Grid Profile

, select and apply a grid profile to the devices.

E )  When prompted to start a device scan, tap 

OK

.

The Device Communications LED 

 flashes green while scanning, solid 

green when all the devices you installed are communicating, or solid amber 

if any devices are not communicating. 

With both methods

If the Device Communications LED 

  remains solid amber, see 

Trouble-

shooting 

 

b

.

8

IQ Envoy display and controls

Network Communications LED 

Green when IQ Envoy is connected  

to Enlighten.

AP Mode LED

Green when IQ Envoy’s AP Wi-Fi  

network is available.

AP Mode Button

Press to enable IQ Envoy’s AP Mode  

for connecting with a mobile device.  

Hold for 5 seconds to start WPS  

connection to a router. 

Power Production LED 

Green when microinverters are  

producing power.

Device Communications LED

Green when devices are  

communicating with IQ Envoy.

Device Scan Button

Press to start/stop 15 minute scan for  

devices over the power line.

Track system installation progress with the Enphase Installer Toolkit mobile app. 

The LEDs on the IQ Envoy PCB (printed circuit board) are solid green when a 

function is enabled or performing as expected, flashing when an operation is in 

progress, or solid amber when troubleshooting with Installer Toolkit is required. For 

a legend of all LED states, see Troubleshooting

a

.

Enphase Installer 

Toolkit mobile app

Содержание NPR-3P-208-NA

Страница 1: ...tains Production CTs wired to the included IQ Envoy Use the Three Phase NPR to support the AC connections needed for an Enphase commercial solar installation The Three Phase NPR provides electrical connection between a three phase electrical grid and a three phase PV array During connection it monitors voltages on all three phases and if conditions occur loss of phase under over voltage etc that r...

Страница 2: ... the Wiring Table NOTE Enphase IQ Series Microinverters use a two wire system and do not use a Neutral However the IQ Envoy in the NPR still requires a Neutral from the load center Warning Risk of equipment damage Observe bend radius requirements when routing wires WIRING TABLE Grid Array Connection Torque 250kcmil 3 0 275 lbs in 2 0 6 120 lbs in Copper conductors only rated minimum 90 C Follow NF...

Страница 3: ...alling CTs it is important to match CT and sense voltage phases Be sure to consistently identify the three AC lines at three points the main load center feed the Envoy and the solar production circuit breaker Wire colors typically black red and blue may not always consistently identify L1 L2 and L3 If in doubt use a multimeter to check 5 NOTE Because of variance in load center design and main powe...

Страница 4: ...rial numbers from the installation map F Tap the Connect button This provisions the scanned devices on the Envoy G When prompted confirm the number of devices that you installed H If your system is in Hawaii or in a region that does not use the Factory Installed Grid Profile select and apply a grid profile to the devices The Device Communications LED lights solid green if all provisioned devices a...

Страница 5: ...al six digits of the IQ Envoy serial number E Launch Installer Toolkit and tap Connect to Envoy F Tap Network G Under Network Configuration tap Cellular The app displays Connec tion Status and an indication of signal strength H Check the connection status and verify that signal strength is at least two bars for adequate data transmission I Close the Three Phase NPR cabinet and lock it with padlock...

Страница 6: ...ck the breaker and wiring starting at the load center If all of the non productive microinverters are on the same branch check the breaker and wiring starting at the junction box for the affected branch If only one or scattered microinverters are not producing power first check to see that the AC connectors are fully seated Next check that each mod ule is providing the required startup voltage for...

Страница 7: ...itation est autorisée aux deux conditions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement Industry Canada and FCC This device complies with Industry Canada license exempt RSS standard s and part 15 of the FCC rules Operation is subj...

Страница 8: ...to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interfer ence to radio communications...

Отзывы: