enphase BRK-100A-2P-240V Скачать руководство пользователя страница 10

      Generator Connections

An auto-start generator can be integrated with the Enphase Storage system 

without the need for any external ATS.  

NOTE: 

This system is only compatible with permanently installed, hardwired 

generators that are non-separately derived as per NEC 250.35(B).
Steps for connecting a generator are listed below:
A )   Wire the L1 and L2 AC wires from the generator into the generator lugs 

on the IQ System Controller 2. 
B )   Ensure that the ground terminal of the generator is connected to the 

ground bar inside IQ System Controller 2. Size the generator’s equipment 

grounding conductor as per NEC 250.122 and generator manufacturer’s 

instructions. 
C )   Connect the neutral wire from generator to an appropriately sized posi-

tion on the neutral bar inside IQ System Controller 2. 

NOTE: 

IQ System Controller 2 does not switch the neutral and the ground 

from the generator. It only switches the feeders i.e., L1 and L2. Therefore, 

the generator needs to be configured as a non-separately derived system.

D )    Buy and install an appropriately sized breaker for the generator on the 

IQ System Controller 2’s busbar and connect the L1 and L2 generator cables 

from IQ System Controller 2’s ATS board to this breaker.

NOTE: 

 The maximum allowed breaker size is 80A. Select an Eaton BR 

breaker model that has the hole for the additional fastener as per NEC 

480.36(D). Available models: BR220B, BR230B, BR240B, BR250B. Eaton 

breaker BR260, BR280 already has the hole.

8

E )   Purchase and install a hold-down screw kit (SKU: EP200G-NA-HD-200A) 

to secure the Generator breaker.
F )   Install a pair of generator CTs (CT-200-SPLIT) for L1 and L2 at the IQ 

System Controller 2’s Generator input terminal for power monitoring when 

the generator is running. Detailed CT wiring is described in step 9. 
G )   Use Enphase Installer App mobile application to commission and pro-

gram IQ System Controller 2 to control the generator.
H )  For 2-wire autostart generators, wire the Generator I/O port in IQ System 

Controller 2 to the 2-wire remote start terminals of the generator. Refer Step 

7 for steps on how to secure the auxiliary contacts to IQ System Controller 

2. Follow local code requirements for wire sizing.
I )     Autostart generators typically require a constant 120 Vac for battery 

charger. This power can be drawn from the backup loads panel protected by 

a breaker so that it is powered even during an outage.
J )   For permanently installed Propane/Natural gas generators, have a certi-

fied contractor install the gas line required to supply the unit.

K )   Some utility-sense based generators like the Generac Guardian come 

with the capability to auto start generators when system goes off grid by 

sensing the absence of the 240V utility power. For such utility-sense based 

remote start generators, install the utility sensing generator start/stop 

control circuit. Wire the primary of a 120V/12V power supply to the backup 

loads panel. Connect the secondary to the Generator auxiliary contact relay 

on the IQ System Controller 2. Wire the other end of the relay to the coil 

of the Normally Close contactor. Connect the contactor to 240V from the 

backup loads panel for utility sensing. Wire the other end of the contactor to 

the Generator through a fuse.

Line diagram for 2-wire remote start generator connection 

Line diagram for utility sense based remote start generator connection

Содержание BRK-100A-2P-240V

Страница 1: ...roviding a consistent pre wired solution for residential applications Along with MID functions it includes PV storage and generator input circuits 2021 Enphase Energy All rights reserved Enphase the Enphase logo IQ System Controller 2 IQ Battery IQ Gateway IQ combiner IQ microinverter Enphase App and other trademarks or service names are the trademarks of Enphase Energy Inc Data subject to change ...

Страница 2: ... for local requirements Washers for use between fastener heads and wall mount bracket Conductors rated at 75 C For sizes refer to the table on the unit and to local codes Over current protection maximum in accordance with local standards The door sheet metal is not required to be grounded since it is pro tected from live parts by other grounded metal and insulating plastic materials thus is consid...

Страница 3: ...w engages with the hole in the bracket to prevent vertical movement of the bracket WARNING Risk of injury and equipment damage Do not skip this step Without these screws in place the IQ System Controller 2 may fall and cause injury or damage if bumped or shaken K Use the four filler plates provided in the lit kit to cover the screws IQ System Controller 2 Wall Mount Bracket Align with stud Bracket...

Страница 4: ...tem Controller and insert quad breaker BRK 20A40A 4P 240V in the NFT position wire L1 and L2 from IQ Gateway terminals through the PV conduit to IQ System Controller wire IQ Gateway L1 and L2 and NFT L1 and L2 to the quad breaker Generator breaker position is free to be used with generator J The bottom right breaker position can be used for the below purposes 1 Power the IQ Gateway 2 Interconnect ...

Страница 5: ...DING ELECTRODE TERMINAL adjacent to the grounding bar From the lit kit place the label SUITABLE FOR USE AS SERVICE EQUIPMENT MAIN SERVICE DISCONNECT on the deadfront near the main breaker service disconnect If IQ System Controller 2 is not used as service equipment these labels should not be used E Connect Lines Neutral and Ground For details refer to the conductor table on the unit for sizes and ...

Страница 6: ...e service entrance of the the system controller The arrows on the Consump tion PCS CT must point towards the loads towards the busbar inside the IQ System Controller 2 Refer to the image on the next page for the Consumption PCS CT location and wiring to the IQ Gateway D You must protect all PCS controlled busbars and or conductors with suitably rated overcurrent devices that are appropriately size...

Страница 7: ...al Back side 20mm vertical x 20mm Horizontal Production CT CT 200 SOLID 9mm vertical x 30mm horizontal This sensor is part of a Power Control System Do not re move or disable Replace with same type and rating NOTE The maximum operating currents in controlled busbars or conductors are limited by the settings of the Power Control System PCS and may be lower than the sum of the currents of the connec...

Страница 8: ... is for connecting with a remote RSD switch It has two normal ly close auxiliary contacts NC3 NC4 and each auxiliary contact has two terminals Gen I O has one normally open auxiliary contact NO3 for generator control and this contact has three terminals All the auxiliary contact relays are rated for pilot duty at 24Vac Vdc nomi nal and 1 Amp A Auxiliary Contact connections for shedding excess PV a...

Страница 9: ...s to secure the headers to IQ System Controller 2 as shown in Feed through headers for I O 1 and I O 2 image 1 Insert the wires from the transformer controller and the external contactor into the feed through header NOTE Supports AWG 28 to AWG 16 wire sizes 2 Tighten the screws on the top torque 0 22Nm to 0 25Nm to secure the wires Follow same procedure for generator dry contact connections There ...

Страница 10: ...of generator CTs CT 200 SPLIT for L1 and L2 at the IQ System Controller 2 s Generator input terminal for power monitoring when the generator is running Detailed CT wiring is described in step 9 G Use Enphase Installer App mobile application to commission and pro gram IQ System Controller 2 to control the generator H For 2 wire autostart generators wire the Generator I O port in IQ System Controlle...

Страница 11: ...he arrow on the CT pointing towards the Generator breaker D Clamp the unmarked CT on Line 2 of the generator branch circuit inside the IQ System Controller 2 box with the arrow pointing towards the Generator breaker E Bring the CT lead wires out of IQ System Controller 2 to the standalone IQ Gateway or IQ Gateway in the IQ Combiner box F Use a screwdriver to loosen the screw on the IQ Gateway term...

Страница 12: ... to meet warranty requirements the IQ System Controller 2 must be installed and or stored according to the instructions in this guide NOTE The IQ System Controller 2 is compatible only with the IQ Combiner 4 4C fitted with USB hub USB radios and production and Consumption PCS CTs The IQ Combiner with the IQ Gateway inside is required for operation of the IQ System Controller 2 Earlier versions of ...

Отзывы: