2.3 Operating Modes
2.3.1 Hardware enabled Operating Modes
The following operating modes can be configured by the encoding inputs CODE_2..0. The
operating mode is defined with pin status at power-up; a change of operation mode is possible
with cleared ID memory only.
Mode
Function
Output signal description
No. of
channels
CODE
_2
CODE
_1
CODE
_0
0
None
NC
NC
NC
1
None
NC
NC
GND
2
Simple switch
actor
Supplies the desired logic switching
state “on/off” at OUT_0 (1 channel)
1
(OUT_0)
NC
GND
NC
3
None
NC
GND GND
4
None
GND
NC
NC
5
None
GND
NC
GND
6
None
GND GND
NC
7
Test
Reserved (factory test mode)
GND GND GND
2.3.2 Firmware enabled Operating Modes
Each RCM 152 receiver can be assigned, either a maximum of 30 EnOcean PTM radio switches,
or up to 2 EnOcean easyfit STM 250 radio window contacts. Learning of mixed PTM and STM
transmitters is not possible. By assigning the first transmitter the Firmware Operating Mode is
defined. The Firmware Operating Mode can only be changed at empty ID memory, e.g. after
deleting all transmitters with the CLR button.
a) Mode RADIO SWITCH
: Each assigned transmitter can be used to change the switching
state of the receiver. It is possible to switch ON (button I) with one switch and OFF (button O)
with another switch.
Initialization:
After Power-up and Learning Phase the module output OUT_0 is
inactive (“off”). At least one of the learned radio switches have to be operated to switch
the output.
b) Mode RADIO WINDOW CONTACT
: If at least one of the assigned window contacts is
open the switching state of the receiver is ON. If both contacts are closed the state is OFF.
Time Out:
The radio window contacts are transmitting a life signal typically every 15
min (5…30 min). 60 min (± 10%) after reception of the last life signal the receiver
considers this contact to be closed.
Initialization:
After Power-up and Learning Phase the module output OUT_0 is
inactive (“off”). At least one of the learned magnet contacts have to be opened to
release the output immediately (before first incoming presence signal).