USER MANUAL V0.8
© 2009 EnOcean | www.enocean.com
PTM 33x / 33xC User Manual V0.8 | Page 10/20
PTM 33X / 33XC
2.7
Radio telegram
2.7.1
Normal operation
In default configuration PTM 33x transmits the same telegrams as a PTM 200 radio switch:
Telegram type RPS: There are two message types depending on how many buttons
(A0, A1, B0, B1) have been pressed (connected to GND)
o
N-message: Only one or two buttons have been pressed.
o
U-message: No pushbutton was pressed when activating the energy genera-
tor, or more than two pushbuttons have been pressed.
Unique factory programmed 32 bit ID
DATA_BYTE2, DATA_BYTE1, DATA_BYTE0=0
DATA_BYTE3 and STATUS as follows:
N-message:
DATA_BYTE3:
7 0
RID UD
PR SRID
SUD
SA
RID
(2 bit)
Rocker ID, A=0, B=1
UD (1
bit)
UD=1
Æ
O-button, UD=0
Æ
I-button
PO
(1 bit)
Polarity, see table below
SRID
(2 bit)
Second Rocker ID
SUD
(1 bit)
(Second) SUD=1
Æ
O-button, SUD=0
Æ
I-button
SA (1
bit)
SA=1
Æ
Second action (2 buttons pressed
simultaneously), SA=0
Æ
No second action
STATUS:
7 0
Reserved T21 NU
RP_COUNTER
Reserved
(2 bit)
For future use
T21 (1
bit)
1
NU (1
bit)
NU=1
Æ
N-message.
RP_COUNTER
(4 bit)
Repeater level: 0 is original message (not repeated)