PTM 240C
2.3
PTM 240C Radio Telegram
2.3.1
Transmission timing
The transmission timing of the radio module PTM 240C has been developed to avoid possi-
ble collisions with data packages of other EnOcean transmitters as well as disturbances
from the environment.
With each transmission cycle, up to 3 identical subtelegrams are transmitted. The transmis-
sion of a subtelegram lasts approximately 1.2 ms. To optimize data security, each telegram
is repeated several times within about 40 ms, whereas the delay between the second and
the third transmission burst is effected at random.
2.3.2
Telegram Data
The PTM 240C transmits an EnOcean radio telegram according to profile 0b000111 – Occu-
pancy Sensor - type 0b0000001 as defined in “Standardization EnOcean Communication
Profiles V1.03”.
For detailed information on the serial protocol please refer to the user manual of TCM2xyC
and the above standardization document.
A teach-in telegram is transmitted, if SW2 is connected to SW_HIGH. This telegram con-
tains the above mentioned profile an type information as well as a manufacturer ID which is
0b11111111111 (multiuser ID) in this case.
In case SW2 is left open the module transmits a data telegram with the information about
the status of the PIR sensor which has to be coded using SW1.
The information transmitted is:
Unique factory programmed 32bit ID
ORG, Data3, Data2, Data1, Data0 and Status as follows:
R=repeater counter
SW1
SW2
ORG Data3 Data2 Data1 Data0 Status Description
open
open
0x07 0xFF
0xFF
0x00
0xFF
0x0R
PIR OFF
SW_HIGH open
0x07 0xFF
0xFF
0xFF
0xFF
0x0R
PIR ON
open
SW_HIGH 0x07 0x1C
0x0F
0xFF
0x80
0x0R
Teach-in
SW_HIGH SW_HIGH 0x07 0x1C
0x0F
0xFF
0x80
0x0R
Teach-in