background image

LED Zone Controller 0-10V Installation Guide  

© 2017 EnOcean GmbH    V2.0 

 

Page  7 

 

8.

 

Remote Commissioning Parameters 

 

 

 

 

 

 

 

 
 
 

 
 

 

 

 

 

Parameter 

Description 

Default / 

Notes 

Light Level Sensor Parameters

 

DaylightingMode  2-level or 5 point continuous 

daylight dimming 

5 point 

PhotoOnThres 

In case of 2-level mode, light is 
switched to MaxVoltageLevel if 
light level is below PhotoOnThres

 

<200lux 

PhotoOffThres 

In case of 2-level mode, light is 
switched to MinVoltageLevel if 
light level is above PhotoOffThres

 

>400lux 

LEV1…5 

Defines 5 input light levels for 
open loop dimming curve 
(LEV1<LEV2<...<LEV5)

 

100, 200, 400, 
600, 800 lux 

OUT1…5 

Defines the LED controller output 
values for the corresponding input 
light levels

 

100, 100%, 60%, 
20%, 0% 

RAMP12, 23, 34, 
45 

Ramp speeds between light levels 
1 and 2, 2 and 3, 3 and 4 , 4 and 5

 

1%/s 

LlsAdjustment-
Delay 

Time before the light level sensor 
can adjust the output light level 
after it was set by the user 

15 min 

LlsEnable-
CurveAdjustment 

Enables or disables user 
adjustment of the 5 point 
dimming curve using triple click 
on the “I” button 

ON (enabled) 

Generic Sensor Parameters (Occupancy and Light Level)

 

SensorRamp-

UpSpeed

 

Ramp-up speed when change is 
triggered by an occupancy or light 
level sensor (2 point mode)

 

20%/s 
0= No ramp 
(immediate)

 

SensorRamp-

DownSpeed

 

Ramp-down speed when change 
is triggered by an occupancy or 
light level sensor (2 point mode)

 

20%/s 
0= No ramp 
(immediate)

 

 

 

 

Parameter 

Description 

Default / 

Notes 

Rocker Switch Parameters

 

RockerSwitch-

OnSpeed

 

Ramp-up speed when rocker 

input request light switch ON

 

20%/s                 
0= No ramp 
(immediate)

 

RockerSwitch-

OffSpeed

 

Ramp-down speed when rocker 

input request light switch OFF

 

20%/s                 
0= No ramp 
(immediate)

 

RockerDim- 

UpSpeed

 

Ramp-up speed when rocker 

input request light dim UP

 

20%/s                 
0= No ramp 
(immediate)

 

RockerDim-

DownSpeed

 

Ramp-down speed when rocker 

input request light dim DOWN

 

20%/s                 
0= No ramp 
(immediate)

 

RockerSwitch-

AutoOffTimer 

Delay after last switch action 

before light is switched OFF 
automatically 

0 (disabled) 

RockerDimEnable  Enables or disables dimming via 

rocker switch 

ON (enabled) 

Occupancy Sensor Parameters

 

OccAutoOn  

 

Defines if a signal from an 
occupancy sensor automatically 
switches on lights (True/False) 

FALSE if at least 
one switch is 
linked, 
otherwise TRUE

 

OccAutoOnLevel

 

Dimming value at which light is 
switched on in case of Auto ON 
event from occupancy sensor 

100%

 

OccAutoOnDelay  Time before the occupancy sensor 

can switch the light back ON in 
Auto ON Mode after the user 
switched it OFF 

15 min 

OccAutoOffTimer

 

Time after which lights will be 
switched to OccAutoOffLevel in 
case of no motion 

15 min 

0=disabled

 

OccAutoOffLevel

 

Dimming value to which lights will 
be dimmed after an occupancy 
sensor Auto OFF timer event 

0%

 

VacancyGrace-
Timer

 

If occupancy is detected within 
the VacancyGraceTimer period 
after an occupancy Auto OFF 
event, lights are turned back ON 

45 s

 

Содержание LEDD

Страница 1: ...ntrollers n Installs inside or mounts to electrical box using threaded connector n Supports wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 11 0 V 13 2 V DC Supply Current typ 16 mA 12VDC supply no sourcing 38 mA 12VDC supply 10V 20mA sourcing Power Consumption 200 mW 12 V DC excluding 0 10V sourcing power 460 mW 12 V DC at maximum 0 10V sour...

Страница 2: ...enna as shown in figure A 4 Restore power to the circuit 5 Use the setup interface to link devices and configure settings refer to the Linking Configuration sections WARNING Move the module away from any power line before using the local setup interface 3 Device Configuration The LED controller can be configured in two ways n By user input to the local setup interface This approach is used for bas...

Страница 3: ...e will stop after 30 seconds if no LRN telegram is received 2 For the transmitter to be linked do one of the following according to the type of device A Sensor click the designated link button B Rocker Pad click the I button top button marked on the switch plastic or I symbol on the back of the switch 3 times quickly 3 If the device has been linked successfully the LRN LED will display solid green...

Страница 4: ...rtly press DIM and LRN button simultaneously to store this value 5 Operating modes The LED Controller supports the following operation modes based on different types of connected devices Mode Default Action Title 24 Compliance Switches only Manual DIM or ON OFF No Occupancy sensors only Auto ON Auto OFF default Auto OFF after 15 minutes No Occupancy sensors and switches Manual DIM or ON Auto OFF C...

Страница 5: ...tion for a period defined by OccAutoOffTimer default 15min then light is set to OccAutoOffLevel default 0 Auto OFF function Ramp up SensorRampUpSpeed speed for Auto ON and ramp down SensorRampDownSpeed speed for Auto OFF are configurable default 20 per second Occupancy Sensors and Switches Light can be switched ON OFF manually function as described above Time based automatic switch OFF as defined ...

Страница 6: ...meter to 0 will cause all messages to be repeated Note 2 level repeating function and repeating of all messages RepeatLinkedDevicesOnly OFF should only be used if really needed Otherwise the system function can be compromised by collisions of telegrams Status messages The LED controller will transmit a status message EEP D2 40 00 after change of its output state or after StatusMessageTimer has ela...

Страница 7: ...y or light level sensor 2 point mode 20 s 0 No ramp immediate Parameter Description Default Notes Rocker Switch Parameters RockerSwitch OnSpeed Ramp up speed when rocker input request light switch ON 20 s 0 No ramp immediate RockerSwitch OffSpeed Ramp down speed when rocker input request light switch OFF 20 s 0 No ramp immediate RockerDim UpSpeed Ramp up speed when rocker input request light dim U...

Страница 8: ...usMessage Timer Defines how often status messages are transmitted seconds 0 off 0xFFFF only event based 0xFFFF RepeaterFunction Defines the repeater level of the device OFF 1 Level 2 Level OFF disabled RepeatLinked DevicesOnly Configures the repeater to only repeat telegrams from devices linked to it ON enabled Enable DebugMessages Enable or disable debug messages OFF disabled EnableLink Checker E...

Отзывы: