LED Zone Controller 0-10V Installation Guide  

© 2017 EnOcean GmbH    V2.0 

 

Page  5 

 

Switches only 

Short click (<0.7s) on “I” button: Light comes ON and 
brightens to most recent dimming value stored before 
device was switched OFF.  
If a light level sensor is linked, then light will be set 
according to its input (see below). The minimum initial light 
level in this case is MinVoltageLevel (default 1.0V). 
Double click (<0.7s) on “I” button: Light is switched ON at 
MaxVoltageLevel (default 10.0V). 
Short click (<0.7s) or double click (<0.7s) on “0” button: The 
current light level is stored, light is dimmed down to 
MinVoltageLevel and then switched OFF. 
Ramp up (RockerSwitchOnSpeed) and ramp down 
(RockerSwitchOffSpeed) speeds for rocker switch operation 
are configurable (default 20% per second). 
Press and hold “I” / “0” button: Light is brightened / dimmed 
until button is released or MinVoltageLevel / 
MaxVoltageLevel is reached.  
Ramp up (RockerDimUpSpeed) and ramp down 
(RockerDimDownSpeed) speeds for rocker dim operation are 
configurable (default 20% per second).  
Rocker-based dimming can be disabled by setting 
RockerDimEnable = OFF. In this case light will be switched 
ON / OFF immediately upon pressing the “I” / “O” button. 
Light can be switched OFF automatically in absence of a 
linked occupancy sensor if no user (switch) action occurs 
during a period defined by RockerSwitchAutoOffTimer.  
This feature can be disabled by setting 
RockerSwitchAutoOffTimer = 0. This feature is automatically 
disabled if an occupancy sensor is present. In this case, 
automatic switch OFF of the light will be performed based 
on the input from the occupancy sensor as described below. 

 

Occupancy Sensors only 

If at least one sensor detects motion, light is switched ON - 
Auto ON function. Light level is set to OccAutoOnLevel 
(default 100%) if no light level sensor is linked.  
Otherwise light level is set according to the natural light 
level reported by the light level sensor as described below. 
If none of the linked occupancy sensors reports motion for a 
period defined by OccAutoOffTimer (default 15min) then 
light is set to OccAutoOffLevel (default 0%) - Auto OFF 
function.  

Ramp up (SensorRampUpSpeed) speed for Auto ON and 
ramp down (SensorRampDownSpeed) speed for Auto OFF 
are configurable (default 20% per second). 

 

Occupancy Sensors and Switches

 

Light can be switched ON / OFF manually, function as 
described above.  Time-based automatic switch OFF (as 
defined by RockerSwitchAutoOffTimer) is always disabled if 
at least one occupancy sensor is linked. 
If no presence has been reported by any of the linked 
occupancy sensors and no switch input has been received 
during a period defined by OccAutoOffTimer (default 15min), 
then light will be set to OccAutoOffLevel (default 0%).  
Light will be automatically turned back ON at the last state if 
occupancy is reported within the VacancyGraceTimer period 
(default 45s) after such Auto OFF event even if the Auto ON 
function is disabled. 
The system can also be configured (OccAutoOn = TRUE) to 
automatically switch ON the light as described above. 
If the user has switched the light OFF (by a linked switch) 
then it can be turned ON again by occupancy sensor input 
only after OccAutoOnDelay (default 15 minutes). 

 

Light Level Sensor

 

One light level sensor can be linked to enable open-loop 
dimming for daylight harvesting. The system then adjusts 
the output light level according to incoming natural light.  
The light level sensor should therefore be placed at a 
position facing the window or skylight where it is not or only 
minimally influenced by light from the fixtures. 
If a light level sensor is linked, the LED controller will by 
default activate daylight harvesting with continuous open 
loop dimming according to a user-defined dimming curve 
based on 5 configurable supporting points.  
Each of these 5 supporting points defines the output light 
level (OUT1 … OUT5) to be set by the LED controller for a 
given reported natural light level (LEV1 … LEV5).  
For natural light levels below LEV1, output light level OUT1 
is set. Likewise, for natural light levels above LEV5, output 
light level OUT5 is set.  
Linear interpolation is used between the defined points (e.g. 
between LEV1/OUT1 and LEV2/OUT2). 

Содержание LEDD

Страница 1: ...ntrollers n Installs inside or mounts to electrical box using threaded connector n Supports wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 11 0 V 13 2 V DC Supply Current typ 16 mA 12VDC supply no sourcing 38 mA 12VDC supply 10V 20mA sourcing Power Consumption 200 mW 12 V DC excluding 0 10V sourcing power 460 mW 12 V DC at maximum 0 10V sour...

Страница 2: ...enna as shown in figure A 4 Restore power to the circuit 5 Use the setup interface to link devices and configure settings refer to the Linking Configuration sections WARNING Move the module away from any power line before using the local setup interface 3 Device Configuration The LED controller can be configured in two ways n By user input to the local setup interface This approach is used for bas...

Страница 3: ...e will stop after 30 seconds if no LRN telegram is received 2 For the transmitter to be linked do one of the following according to the type of device A Sensor click the designated link button B Rocker Pad click the I button top button marked on the switch plastic or I symbol on the back of the switch 3 times quickly 3 If the device has been linked successfully the LRN LED will display solid green...

Страница 4: ...rtly press DIM and LRN button simultaneously to store this value 5 Operating modes The LED Controller supports the following operation modes based on different types of connected devices Mode Default Action Title 24 Compliance Switches only Manual DIM or ON OFF No Occupancy sensors only Auto ON Auto OFF default Auto OFF after 15 minutes No Occupancy sensors and switches Manual DIM or ON Auto OFF C...

Страница 5: ...tion for a period defined by OccAutoOffTimer default 15min then light is set to OccAutoOffLevel default 0 Auto OFF function Ramp up SensorRampUpSpeed speed for Auto ON and ramp down SensorRampDownSpeed speed for Auto OFF are configurable default 20 per second Occupancy Sensors and Switches Light can be switched ON OFF manually function as described above Time based automatic switch OFF as defined ...

Страница 6: ...meter to 0 will cause all messages to be repeated Note 2 level repeating function and repeating of all messages RepeatLinkedDevicesOnly OFF should only be used if really needed Otherwise the system function can be compromised by collisions of telegrams Status messages The LED controller will transmit a status message EEP D2 40 00 after change of its output state or after StatusMessageTimer has ela...

Страница 7: ...y or light level sensor 2 point mode 20 s 0 No ramp immediate Parameter Description Default Notes Rocker Switch Parameters RockerSwitch OnSpeed Ramp up speed when rocker input request light switch ON 20 s 0 No ramp immediate RockerSwitch OffSpeed Ramp down speed when rocker input request light switch OFF 20 s 0 No ramp immediate RockerDim UpSpeed Ramp up speed when rocker input request light dim U...

Страница 8: ...usMessage Timer Defines how often status messages are transmitted seconds 0 off 0xFFFF only event based 0xFFFF RepeaterFunction Defines the repeater level of the device OFF 1 Level 2 Level OFF disabled RepeatLinked DevicesOnly Configures the repeater to only repeat telegrams from devices linked to it ON enabled Enable DebugMessages Enable or disable debug messages OFF disabled EnableLink Checker E...

Отзывы: