background image

Occupancy Sensor - Wall Mounted

Installation Guide

Model:  EOSW

Package Contents

 

Occupancy Sensor

 

2 screws, 2 wall anchors

 

1 wide angle lens  

(installed)

 

1 long range lens

Product Description

The wall-mounted Occupancy Sensor saves energy and adds 

convenience by accurately detecting when an area is occupied 

or vacant. 
It is wireless, solar-powered, and uses a passive infrared (PIR) 

sensor to detect motion. The occupancy sensor transmits RF sig-

nals that control lighting, HVAC, and outlets to manage building 

energy consumption more efficiently.
Features Include: 

 

Sends wireless signals to receiving devices whenever  

motion is detected

 

Harvests indoor light to power the sensor and wireless  

communications

 

Mounts flush on the wall or in a corner; adjustable ceiling 

corner bracket sold separately

 

Works with other sensors for enhanced occupancy tracking

 

Interchangeable lenses for tailored sensor coverage

 

Built-in tests to confirm operation at installed location

 

Supplemental battery or alternative power supply options for 

extreme low-light conditions

Specifications

Power Supply Indoor light energy harvesting 

(Optional) Supplemental battery or 

2-wire connector for external power 

or remote solar cell (3-5VDC)

Transmission Range 80 ft. (25 m)

Radio Frequency EnOcean 315 MHz,  

ISO/IEC 14545-3-10 standard

Light Required to  

Sustain Operation

50 lux for 30 transmissions/hour 

100 lux for 60 transmissions/hour

Charge Time  

before Linking 

2 minutes @ 50 lux

Charge Time for  

Full Charge 

3 hours @ 200 lux (after startup) 

6 hours @ 200 lux (cold start)

Operating Life in Dark-

ness (after full charge)

48 hours

EEP (EnOcean  

Equipment Profile)

A05-07-01

Heartbeat  2 - 12 mins., randomized

Dimensions 5.83” L x 2.52” W x 1.8” D 

(148 mm x 64 mm x 45.7 mm)

Weight 4.09 oz. (116 g)

Environment Indoor use only

14° to 104°F (-10° to 40°C)
20% to 95% relative humidity 

(non-condensing)

Agency Compliance FCC, IC

Functional Description 

If occupation is detected by the permanently active PIR sensor, 

a radio telegram indicating the occupied status will transmit 

immediately. An internal timer starts to run with a variable timer 

length. The timer value may vary between 60 and 300 seconds, 

depending on the light level.  No radio telegrams will be sent 

out when the timer is counting down.
After the timer has finished the countdown, the unit will trans-

mit again if occupancy was detected during the countdown time 

period. If occupancy was not detected, the unit will transmit a 

heartbeat signal - sending the unoccupied status with a ran-

dom timing of 2 to 12 minutes. There are two buttons which 

allow entrance to a “Walk” or “Light-level” test mode.  These 

test modes are for installation purposes only and will be exited 

automatically after 3 minutes.

Tools Required

 

Power drill, 3/16” bit

 

Screwdriver

 

Leveling tool

 

Light meter

 

Battery (CR2032) for testing

Page 1

64mm

148mm

5.8”

2.5”

Solar Cell

Lens

Button

Interface

45.7mm

1.8”

28mm

1.1”

Содержание EOSW

Страница 1: ...0 lux for 30 transmissions hour 100 lux for 60 transmissions hour Charge Time before Linking 2 minutes 50 lux Charge Time for Full Charge 3 hours 200 lux after startup 6 hours 200 lux cold start Operating Life in Dark ness after full charge 48 hours EEP EnOcean Equipment Profile A05 07 01 Heartbeat 2 12 mins randomized Dimensions 5 83 L x 2 52 W x 1 8 D 148 mm x 64 mm x 45 7 mm Weight 4 09 oz 116 ...

Страница 2: ...ong Range Coverage 16 ft 0 16 ft 8 ft 8 ft Top View 27 77 21 5 14 6 5 center line Side View 6 8 ft 2 1 m 3 ft 1 m 7 ft 2 2 m 10 ft 3 m 35 ft 10 7 m 60 ft 18 3 m 100 ft 30 5 m Installing The mounting plate can be installed flush to the wall or angled in a corner NOTE It may be easier to link the sensor before it is mounted on the wall See the Linking section 1 Remove the mounting plate from the sen...

Страница 3: ...e transceiver controller installation guides to complete the linking process Testing the Sensor Before starting a test ensure the sensor s energy storage is fully charged by placing it under bright light at least 200 lux for 20 minutes or insert a battery for 5 minutes If a battery is used to charge the sensor for a light test ensure it is removed to get an accurate light measurement A test mode w...

Страница 4: ...oit pas produire de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi meme si le brouillage est susceptible d en compromettre le fonc tionnement IMPORTANT Tous les changements ou modifications pas expressément approuvés par la partie responsable de la conformité ont pu vider l autorité de l utilisateur pour actioner cet équipment Limited Warranty Subjec...