2.
Select the Switched Auto-Off
menu.
3. Select an option.
4.
Save the selection.
To change the motion auto-off option:
This example shows changing the option from 15 to 5 minutes.
1. Access Basic Setup mode.
2.
Select the Motion Auto-Off
menu.
3. Select an option.
4.
Save the selection.
Vacancy Check
Vacancy check is a time delay activated when a door sensor
opens and closes. Linked loads will turn off if any motion
sensor(s) does not confirm
occupancy within the time delay.
From the Vacancy Check menu,
the active option is indicated
by the number of green blinks
on the Set LED; amber blinks
indicate an unsaved change.
Click the Set button an appro
-
priate number of times to select
an option.
To change the vacancy check option:
This example shows changing the option from 5 to 15 minutes.
1. Access Basic Setup mode.
2.
Select the Vacancy Check
menu.
3. Select an option.
4.
Save the selection.
To enable the device as a repeater
In some situations, enabling the transceiver device as a repeater
can help optimize the wireless range between devices.
1.
Access Advanced Setup by holding both buttons down for 5
seconds and releasing them when both LEDs turn amber.
2.
Click the Set button an
appropriate number of
times to select an option.
By default, the first menu
option in advanced setup is
to Enable Repeater.
Option
Clicks Blinks
5 minutes
15 mins. (default)
30 minutes
60 minutes
120 minutes
Option
Clicks Blinks
Disabled
(default)
1 Hop
2 Hops
Example: Setting a device to operate as a repeater.
1.
Access the Advanced setup (hold down both buttons for 5
seconds - until both LEDs turn amber).
2.
Select “option 2” by clicking the Set (right) button two times.
(Set button LED will blink 2x (amber) to confirm)
3.
Save selection by holding Set button for 2 seconds.
4. Exit Menu (hold both buttons for 2 seconds.)
5.
Reboot module by either power cycling or pressing and
holding both buttons for 10 seconds (release when Left
LED=Red, Right LED=Green).
Troubleshooting
Problem
Solution Checklist
The device does not
power up
▪
Check the wiring for errors
▪
Check the circuit breaker
▪
Use a voltage meter to confirm power
The device does not
control linked load
▪
Click the Set button to open/close the relay
manually
▪
Turn off the power and then restore it
Cannot link other
devices
▪
Check if Accept Link option can be accessed
▪
Move closer to the device; it may be out of
range
▪
Try linking a different device
▪
Check for environmental conditions that inter
-
fere with RF signals
▪
Verify the maximum number of devices (14)
has not been exceeded
Cannot change set-
tings on the device
▪
Check if menu item can be accessed
▪
Check if changes can be saved
The device does not
respond to wire-
less messages or
selected settings
▪
Check for environment or range issues
▪
Verify the device is linked
▪
Check if appropriate devices are linked accord
-
ing to good system planning
▪
Extend the antenna to amplify the range:
remove it from the groove in the module,
straighten it and slide it into the white antenna
sleeve provided
Contains: 902 MHz:
FCC: SZV-STM300U
315 MHz:
FCC: SZV-STM300C
IC: 5713A-STM300U
IC: 5713A-STM300C
This device complies with part 15 of the FCC rules and Industry Canada ICES-003. Operation is subject
to the following two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired operation.
IMPORTANT! Any changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate this equipment.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts
de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) l’appareil ne doit pas produire
de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, meme
si le brouillage est susceptible d’en compromettre le fonctionnement.
IMPORTANT! Tous les changements ou modifications pas expressément approuvés par la partie
responsable de la conformité ont pu vider l’autorité de l’utilisateur pour actioner cet équipment.
In-line Switch Module • Installation Guide
Page 4
© 2015 EnOcean GmbH
V2.5 XISMIGEOA