background image

The Menu LED or Set LED display solid for a number of sec

-

onds in a certain color to indicate a mode or a confirmation.
The Menu LED blinks a number of times in a color to indi

-

cate a selected menu.

The Set LED blinks a number of times in a color to indicate 

an option.

A number in a white box indicates the number of times to 

click the Menu button or Set button.
A number in a black box indicates the number of seconds to 

hold down the Menu button or Set button.

To link a transmitter to a transceiver

1.  Access Basic Setup mode.  

 

NOTE:

 By default, the Accept Link option in the Linking 

menu is selected. Once activated, this option stays active for 

two minutes to provide time to link multiple devices. 

 

 

Ready to accept links.

2. 

For the transmitter to be linked, do one of the following ac

-

cording to the type of device:

A. 

Sensor: click the designated link button.

B. 

Key Card Switch: insert/remove the card 3 times quickly.

C. 

Rocker Pad: click the top button 3 times quickly.

 

 

Device linked successfully. 

 

Set LED displays solid 

 

green for 3 seconds. 

The relay will toggle once to indicate a successful learn in. 

After a device is linked, additional learn telegrams from 

that device will cause the relay to toggle once.

 

 

Ready to accept new links.

3. 

To exit mode and return to normal operation, press and hold 

both buttons for 2 seconds.

To unlink a device

 

Follow the same steps as described in the “To link...” section 

above with the following deviations: 

 

After step 1 in the “To link...” section above, click the “Set” 

(right) button 3 times to enable the “Remove Link” option. 

 

 

Ready to remove links. 

 

Follow the same instructions as shown in Step 2 of the “To 

link...” section. The Set (right) LED will turn red briefly to indi

-

cate the link was successfully removed.

To restore factory defaults

Follow these steps to clear all linked devices and restore the In-

line Switch Module to its factory default settings.

1. 

Press and hold both buttons for 15 seconds

 

Hold buttons until the Menu (left) LED is solid RED and the 

Set (right) LED is solid Amber (Both LEDs will turn various 

colors as the module cycles through the resetting process.

2. 

Press and hold the Set (right) button for 3 seconds to con

-

firm factory reset.

3. 

Device will reboot.

Configuring

The default settings on the module support common control 

and installation scenarios. However, some occupancy settings 

can be adjusted on the module using the setup interface, if 

required.

Setting

Default

Application

Auto-On

Automatically 

Determined

If linked to an occupancy sen

-

sor, the default is Enabled.
If linked to a switch, the default 

is Disabled for manual control.

Vacancy Check 

15 minutes

If linked to a occupancy senor 

and a door sensor.

Switched Auto-Off 

Disabled

If linked to a rocker pad or key 

card switch.

Motion Auto-Off 

15 minutes

If linked to occupancy sensor.

Door/Window Ajar 

2 minutes

If linked to a window sensor or 

patio door.

Egress

30 seconds

If linked to a key card switch.

Auto-Off

There are two auto-off menus, one for occupancy sensors, 

and one for rocker switches. For linked occupancy sensors, 

the default is 15 minutes. For 

linked rocker pads and key card 

switches, the default is Disabled 

to allow manual control. 

From the auto-off timer menu, 

the active option is indicated by 

the number of green blinks on 

the Set LED; amber blinks indicate 

an unsaved change. Click the Set 

button an appropriate number of 

times to select an option.

To change the switched auto-off option:

This example shows changing the option from Disabled to 5 

minutes.
1.  Access Basic Setup mode.  

Option

Clicks Blinks

Disabled 

5 mins.

15 mins.

30 mins.

60 mins.

In-line Switch Module • Installation Guide