Product Description
The In-Line Switch Module provides a simple and effective way
to conserve energy and enhance convenience by intelligently
switching lighting and other electrical loads.
The module communicates wirelessly with other EnOcean-based
products used for occupancy detection and lighting control. The
module is a line voltage control device compact enough to be
mounted inside a standard electrical junction box or mounted to
an electrical box or a lighting fixture through a standard knock-
out using the threaded connector.
Features Include:
▪
Receives wireless messages from other devices to switch
lighting or other electrical loads on/off
▪
Controls loads individually or as part of a scene or event
▪
Installs inside or mounts to electrical box using threaded
connector
▪
Sends wireless messages to other controlled devices and
configurable transceivers.
Specifications
Power Supply
120V - 277V VAC, 50/60 Hz
Maximum Load
General Purpose: 16A @ 120/277VAC
Resistive: 16A @ 120/277VAC
Motor: 1/2 HP @ 120VAC
Tungsten: 960W @ 120VAC
Ballast: 600W @ 120VAC
Power Consumption 1.1W full load, 500mW quiescent
Surge Protection
3kV line to line, exceeding
IEC61000-4-5 installation class 4
Inputs/Outputs • Flying-lead style power input wires
• 1 normally open relay
• 1 switched output wire
• Radio Frequency (RF) transceiver
• 2 Buttons with LEDs for device
configuration & manual control
RF Communications EnOcean 902 MHz (EISMU)
EnOcean 315 MHz (EISMC)
Transmission Range
80 ft. (25 m)
EnOcean Equipment Profile
Interoperable Products /
EEPs (EnOcean
Equipment Profiles)
A5-11-01
Rocker Pad Switch (F6-02-02)
Key Card Switch (F6-04-01)
1BS Single Input Contact (D5-00-01)
Occupancy Sensor (A5-07-01)
Occupancy Sensor (A5-07-02)
Occupancy Sensor (A5-07-03)
Contact, Single Input (A5-30-02)
Central Command (A5-38-08)
Dimensions 2.78” H x 1.65” W x 1.1” D
(73mm x 42mm x 28mm)
Weight
3.2oz. (90g)
Mounting
• Install inside standard electrical box
• Connect to electrical boxes and
fixtures using threaded nipple
Environment • Indoor use only
• 32° to 104° F (0° to 44° C)
• 20% to 85% relative humidity
(non-condensing)
Agency Compliance ETL, FCC, IC, UL 2043 Plenum Rated
Planning
Take a moment to plan for the module’s successful operation
and optimal communication with other system components.
▪
Always use a qualified installer
▪
Install in an appropriate location
▪
Take care not to damage the radio antenna that runs in a
groove on the outside of the module
▪
Consider the construction materials in the space and ob
-
stacles that may interfere with RF signals
Installing
Read and understand instructions completely before starting.
ELECTRICAL SHOCK HAZARD
High Voltage. This device must be installed by
a qualified installer or electrician. Follow all ap
-
plicable electrical codes for installation.
Tools Required
▪
Screwdriver
▪
Wire nuts
Page 1