Configure STM 300 module
STM 300 is designed for multiple applications, therefore no application specific EnOcean
Equipment Profile (EEP) is implemented. To use the auto learn function in DolphinView
(or other EnOcean devices), the EEP profile must be configured first with DolphinStudio:
1.
Start Dolphin Studio and
select „Chip configuration‟
2.
Select the module STM 300
3.
The button „Read configuration‟
shows the default EEP setting:
FUNC: 0x3F, TYPE: 0x7F
4.
For testing the entry has to be
changed into e.g.:
FUNC: 0x10 (room operating panels)
TYPE: 0x03 (temperature sensor 0...40°C,
with set point control)
5.
The button „Write configuration‟ set the
new profile. A rereading of configuration
(button 3) confirmed the successful write
operation.