background image

EOSD - Occupancy Sensor Sub Desk 

  

Installation Guide

 

Copyright EnOcean © 2019 

Page 1 of 4 

EOSD_Installation_Guide_V2.1 

 

Package Contents

 

 

Occupancy Sensor 

 

Desk  mounting  plate  with  double  sided  adhesive  tape 
for easy mounting (screwing optional)  

 

CR2032 battery 

 

 

Product Description 

The Sub-desk mounted Occupancy Sensor is detecting when a 

desk is occupied or vacant based on motion in the space 

underneath the desk.  

This device is wireless, and uses a passive infrared (PIR) sensor to 

detect such motion. The occupancy sensor transmits RF signals 

to control desk power supply or sends people counting 

information to an IoT space utilization system. 

 

Functional Description  

If motion is detected by the permanently active PIR sensor, a 

radio telegram indicating the occupied status will transmit 

immediately. A transmission interval timer starts to run with a 2 

minute lockout timer.  No radio telegrams will be sent out until 

the timer expires.  

After the timer has expired, the unit will transmit occupancy 

upon new motion detection.  An unoccupied message will be 

sent if no motion is detected for an extended period - sending 

the first at 10 minutes, then again at 30 minutes.  A heartbeat 

message can also be enabled (see “Optional Settings”).  

 

Specifications (typ. values)

 

Power Supply: 
        Optional:

 

CR2032 battery   
2-wire connector for external power or 
remote solar cell (3-5 VDC)

 

RF Transmission Range

 

80 ft. (25 m)

 

Battery Life:

 

6.5 yrs

 

Motion Transmission 
Interval

 

2 minutes

 

Unoccupied Transmission

 

10 and 30 minutes since last  motion

 

Heartbeat Transmission 

Interval (unoccupied)

 

Disabled by default 

 

Enabled = heartbeat @ 1 hr interval 

 

(after unnocupied messages)

 

EnOcean Equipment 
Profile 

 

EEP A5-07-01 

 

RF Communications

 

EOSDA: EnOcean 868 MHz  
EOSDU: EnOcean 902 MHz 

 

Dimensions

 

6.30” L x 2.35” W x 1.47” D 

 

(160mm x 60mm x 37mm)

 

Weight

 

4.4 oz. (125 g)

 

Mounting Height

 

2.45-3.15 feet (70 – 90cm) 
recommended

 

Environment

 

Indoor use only

 

14° to 104°F (-10° to 40°C)

 

20% to 95% relative humidity 

 

(non-condensing)

 

Agency Compliance

 

EOSDA: RoHS, CE, RE-D  
EOSDU: FCC, IC

 

 

 
Safety Instructions 

 
Intended use: 

 

This product is intended for indoor usage in closed dry rooms. The product must not 

be used in any relation with equipment that supports, directly or indirectly, 

human/animal health or life or with applications that can result in danger for people, 

animals or real value. The product is not suitable for use in mechanically or 

environmentally challenging environments including (but not limited to) environments 

with heavy vibrations, mechanical shocks, very high humidity, very dusty or in explosive 

atmosphere. The installation and assembly of electrical equipment may only be 

performed by a skilled electrician.  

Basic safety instructions: 

 

Risk of suffocation! Do not leave the packaging material lying around. Children could 

swallow the small parts and choke on them. Install and operate product according to 

user manual and do not modify product. The product should not be exposed to rapid 

temperature changes shortly before or during operation; condensation of moisture has 

to be avoided. Wrong cleaning may damage the product; we suggest cleaning with 

soft and damp tissue.  

Disposal: 

 

Product: Dispose of the used components at an official collection point for electronic 

waste or at your local dealer.  Packing: Please use the recycling operators known to 

you. Germany: WEEE-Reg.-No.: DE 93770561 

Содержание EASYFIT EOSD

Страница 1: ... by default Enabled heartbeat 1 hr interval after unnocupied messages EnOcean Equipment Profile EEP A5 07 01 RF Communications EOSDA EnOcean 868 MHz EOSDU EnOcean 902 MHz Dimensions 6 30 L x 2 35 W x 1 47 D 160mm x 60mm x 37mm Weight 4 4 oz 125 g Mounting Height 2 45 3 15 feet 70 90cm recommended Environment Indoor use only 14 to 104 F 10 to 40 C 20 to 95 relative humidity non condensing Agency Co...

Страница 2: ...d Coverage Diagram Rough reference values The occupancy sensor can be mounted at the sub desk surface with the double sided adhesive If needed screws can also be used to fix the mounting plate NOTE Sometimes it s easier to link the sensor before it is mounted sub desk Refer to the Linking section 1 Remove the sensor from packaging 2 Remove the mounting plate from the sensor 3 Insert the CR2032 bat...

Страница 3: ...he transceiver to which the sensor is linked Refer to the Linking section of the receiver installation guide to complete the linking setup process Use the walk test to confirm that motion is within the sensor s range NOTE Before starting the test ensure the battery is inserted for 5 minutes at least If the sensor does not have a sufficient power it cannot enter into the test mode No LED light or 1...

Страница 4: ...utton to transmit motion message Verify the LED blinks when motion is detected during a walk test Verify the battery is inserted properly Sensor is activated when there is nothing to detect Verify there is 4 ft 1 2 m clearance from heat sources that may disturb sensing Reduce sensitivity setting by moving the PIR sensitivity switch on the back from REG to LOW the left hand position Linked device d...

Отзывы: