Two additional settings can be configured via button presses 

which may be useful in some installations.  Note that these 

settings consume additional energy: 

 

LED Blink on Motion Transmission

 - Red LED under PIR lens 

will blink whenever motion is transmitted (disabled by default). 

••> To enable/disable - press and hold Menu button for 3 

seconds (green Menu LED will blink once) 

  

-Enabled = 3 blinks from green Menu LED   

 

              -Disabled = 3 blinks from red Set LED 
 

Heartbeat Transmission

 - unoccupied heartbeat message will 

be sent at 1 hr intervals with no motion (disabled by default). 

••> To enable/disable - press and hold Menu button for         

5 seconds (both green and red LEDs will blink once) 

  

-Enabled = 3 blinks from green Menu LED  

  

-Disabled = 3 blinks from red Set LED 

 

 

 

 

If needed, an auxiliary 3-5 VDC power source can be used. 

1.

 

Remove the sensor from the mounting plate and identify the 

auxiliary power connector on the circuit board 

2.

 

Insert the 3-5 VDC + and - leads into the appropriate screw 

terminals. 

3.

 

Remount the sensor on the mounting plate.  

 

 
 

Problem

 

Solution Checklist

 

Sensor does not 

 

generate a wireless 
message

 

 

Press Set button to transmit motion message

 

 

Verify the LED blinks when motion is detected 

during a walk test

 

 

Verify the battery is inserted properly

 

Sensor is activated 
when there is 
nothing to detect

 

 

Verify there is 4 ft. (1.2 m) clearance from heat 

sources that may disturb sensing

 

 

Reduce sensitivity setting by moving the PIR 

sensitivity switch on the back from REG to 

 

LOW (the left-hand position)

 

Linked device does 
not respond to 
wireless messages

 

 

Force motion message by pressing Set button

 

 

Check for environment or range issues

 

 

Verify the device is linked

 

 

Check the transceiver connection and the 

wiring for errors

 

 

Check if appropriate devices are linked 

according to good system planning

 

 
 
 
 
 
 

  

868,300 MHz: contains: RE-D, RoHS, REACH 

 

902 MHz:     contains: 

 

   

FCC:  SZV-STM300U  

 

 

 

  

IC:  5713A-STM300U     

 

This device complies with part 15 of the FCC rules and Industry Canada ICES-003. Operation is 

subject to the following two conditions: (1) This device may not cause harmful interference, 

and (2) this device must accept any interference received, including interference that may 

cause undesired operation. 

 

IMPORTANT! Any changes or modifications not expressly approved by the party responsible 

for compliance could void the user’s authority to operate this equipment. 

 

 

WEEE-Reg.-No.: DE 93770561  

 
EnOcean GmbH 
Kolpingring 18a 
82041 Oberhaching

 

Germany 

  

 

Optional Settings  

 

Supplemental Power Supply (Optional)  

 

Troubleshooting 

 

Agency Compliance 

 

Содержание EASYFIT EOSD

Страница 1: ... by default Enabled heartbeat 1 hr interval after unnocupied messages EnOcean Equipment Profile EEP A5 07 01 RF Communications EOSDA EnOcean 868 MHz EOSDU EnOcean 902 MHz Dimensions 6 30 L x 2 35 W x 1 47 D 160mm x 60mm x 37mm Weight 4 4 oz 125 g Mounting Height 2 45 3 15 feet 70 90cm recommended Environment Indoor use only 14 to 104 F 10 to 40 C 20 to 95 relative humidity non condensing Agency Co...

Страница 2: ...d Coverage Diagram Rough reference values The occupancy sensor can be mounted at the sub desk surface with the double sided adhesive If needed screws can also be used to fix the mounting plate NOTE Sometimes it s easier to link the sensor before it is mounted sub desk Refer to the Linking section 1 Remove the sensor from packaging 2 Remove the mounting plate from the sensor 3 Insert the CR2032 bat...

Страница 3: ...he transceiver to which the sensor is linked Refer to the Linking section of the receiver installation guide to complete the linking setup process Use the walk test to confirm that motion is within the sensor s range NOTE Before starting the test ensure the battery is inserted for 5 minutes at least If the sensor does not have a sufficient power it cannot enter into the test mode No LED light or 1...

Страница 4: ...utton to transmit motion message Verify the LED blinks when motion is detected during a walk test Verify the battery is inserted properly Sensor is activated when there is nothing to detect Verify there is 4 ft 1 2 m clearance from heat sources that may disturb sensing Reduce sensitivity setting by moving the PIR sensitivity switch on the back from REG to LOW the left hand position Linked device d...

Отзывы: