background image

EX-5100 C

OMBUSTIBLE

 

 

ENMET 

 

 
 

3.0 Installation of the EX-5100 

C

AUTION

:

 

Area must be declassified during installation.

 

The 

ENMET

 

EX-5100 

gas sensor/transmitter (S/T) is a 3-wire, 24 

V

DC

 4-20 mA S/T for the detection of combustible gas.  The 

S/T is meant to be used in conjunction with an appropriate power supply and controller.  The 

ENMET

 

EX-5100

 

sensor/transmitter is in an enclosure rated for use in a Class I, Div. 1, Groups B, C, D, classified area.  Appropriate wiring, 
conduit and fittings are required for proper installation in a explosion proof rated environment. 

C

AUTION

:

 Since the sensor/transmitter detects gas only at the sensor location, pay attention to the possible sources of gas, the 

density of the gas, locations where the gas may be confined and locations where the gas may damage or injure 
property or personnel, when choosing locations of sensor/transmitters. 

Take into consideration environmental factors when deciding on S/T location.  Avoid locations where the S/T may be damaged 
by liquid immersion, excessive heat or other know hazards.  Also, take precautions to insure condensation inside of the conduit 
does not enter the S/T. 

3.1 Mounting the EX-5100 Enclosure 

Mount the enclosure, using the two mounting holes provided see Figure 2.  Pay particular attention to the source and density of 
the gas being detected when choosing the location.  Mount the S/T near the ceiling for lighter than air gases /vapors and near 
the floor for heavier then air gas/vapors.  Contact 

ENMET

 if you have questions regarding your application. 

C

AUTION

:

 

Before connecting S/T to controller remove the power source to controller.  Failure to do so may cause damage to 

sensitive components. 

 

 

 

Menu

Select

 

 

Figure 2: EX-5100 Mounting Dimensions  

Optional 
Conduit fitting  
Typically: ½

 NPT female 

Mounting Holes 
2 places, 0.313

 

T

OP 

V

IEW

 

Sensor 

Sensor/Transmitter 
Enclosure Top View 

Sensor/Transmitter 
Enclosure Side View 

Sensor 

S

IDE 

V

IEW

 

½

 NPT female 

Содержание EX-5100

Страница 1: ...ENMET PO Box 979 Ann Arbor MI 48106 0979 www enmet com Manual part number 80003 096 MCN 416 04 03 09 EX 5100 COMBUSTIBLE Manual...

Страница 2: ...gs 13 5 4 Sensor Replacement 13 6 0 REPLACEMENT PART NUMBERS 14 7 0 WARRANTY 14 List of Figures and Tables FIGURE 1 EX 5100 FEATURES 2 FIGURE 2 EX 5100 MOUNTING DIMENSIONS 3 FIGURE 3 TERMINAL POSITION...

Страница 3: ...spection and after you have received written acknowledgment of the damage from the carrier contact ENMET Customer Service for return authorization and further instructions Have your Purchase Order and...

Страница 4: ...instrument maintenance functions The switch locations are indicated by MENU and SELECT A magnetic field pulse is applied by momentarily putting the end of the magnet in proximity to the switch and the...

Страница 5: ...tters Take into consideration environmental factors when deciding on S T location Avoid locations where the S T may be damaged by liquid immersion excessive heat or other know hazards Also take precau...

Страница 6: ...e supplied J8 plug then attach to the J8 terminal See Figure 3 for locations J4 PLUG TERMINAL TO CONTROLLER WIRING Position Function 1 24 VDC power 2 GND 3 4 20 mA out 4 RS 485 D 5 RS 485 D Contact EN...

Страница 7: ...l Display Mode If intended function Tap the magnet over SELECT switch Tap the magnet over the MENU switch to advance to the Zero procedure For adjusting Zero If intended function Tap the magnet over S...

Страница 8: ...NOTE Software revision may cause variations of display output Example of Display Function The instrument Model EX 5100 The instrument Serial Number The instrument Software Revision IF the right most c...

Страница 9: ...lay indicates Alarm 1 Set point Tap the magnet over the MENU button Display indicates Alarm 2 Set point Tap the magnet over the MENU button No Function for the SELECT button in this mode Display indic...

Страница 10: ...asurement of target gas Hold the magnet over MENU switch for 2 5 seconds to enter the Maintenance Menu The Power Fault LED will flash Green Red to indicate the EX 5100 is in Maintenance Mode To exit t...

Страница 11: ...nd Span functions are two separate procedures They operate independently of each other It is recommended that the Zero procedure be done prior to the Span procedure ENMET recommends at least quarterly...

Страница 12: ...ne Calibration coefficients relative to Methane have been generated for over 30 different combustible hydrocarbons and solvents A partial list of these gases and vapors are listed in Table 3 Non Stand...

Страница 13: ...ociated calibration gas cylinder to the regulator and calibration cover See to Figure 3 4 Open the valve to apply the calibration gas to the sensor 5 Watch for the signal level to stabilize Refer to T...

Страница 14: ...the magnet over the SELECT switch The MENU switch changes digit indicated by underscore cursor The SELECT switch locks underscored digit and moves to next digit See Section 5 2 2 SELECT mA Span MENU S...

Страница 15: ...see Figure 5 for a detailed maintenance menu flow chart Example of Display Function Normal Display Mode Measurement of target gas Hold the magnet over the MENU switch for 2 4 seconds to enter the Mai...

Страница 16: ...means of transportation is requested during the warranty period the customer is responsible for the difference between the most economical means and the expedient mode ENMET shall not be liable for an...

Страница 17: ...ult in processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a mi...

Страница 18: ...OD Check one K VISA MasterCard______________________ ________ ________ Card number Expiration Card Code K American Express______________________ ________ ________ Card number Expiration Card Code Name...

Отзывы: