A

 

 

W-TRAC

 

 
 

IOM‐49 

                           9 of 12 

Mar 99  R4 

 

 
 

When the outdoor ambient temperature is below 15°F (‐10°C) the speed of the heat wheel will be reduced 
to maintain the leaving exhaust air humidity between 80 – 90%.  This application requires high accuracy 
humidity sensors. 
 

RETURN

 

AIR

 

RH%

 

SENSOR

 

 
This method of frost control requires a RH sensor installed in the equipment return air section, just before 
the heat wheel, wired into terminals RMH and C2.  DIP 3 must be ON, DIP 1 and 2 must be OFF. 
 
Using the values of the RH and ambient (outside air) sensor, the W‐TRAC calculates the minimum 
allowable exhaust air temperature that will keep frost from forming on the wheel. 

 

BDRH

 

PREDICTED

 

RETURN

 

AIR

 

RELATIVE

 

HUMIDITY

 

 
RH% sensing is not used in this method of frost control.  DIP 1 and 3 must be ON, while DIP 2 is OFF. 
 
The W‐TRAC may operate without the use of humidity sensing in situations where the RH% values are 
expected to be reasonably constant.  In these cases, the W‐TRAC operates by sensible temperature only. 
 
When enabled, the BDRH pot (Building Design Relative Humidity) is set according to the expected design 
return air conditions.  Refer to the table below to set the expected values based on temperature and RH%. 

Table 1 

BDRH setting 

Return Air Conditions 

70°F (21°C) 

75°F (24°C) 

80°F (27°C) 

< 25% 

< 21% 

< 18% 

26 – 32% 

22 – 27% 

19 – 23% 

33 – 39% 

28 – 33% 

24 – 27% 

40 – 49% 

34 – 42% 

28 – 35% 

 
To use this table, first select the return air temperature, then select the RH% range in the column below, 
then select the BDRH setting to the left. 

 

WIRING

 

 

The W‐TRAC terminals H and N require a minimum 24 VAC, 40 VA class 2 power supply that does not need 
to be isolated from the rest of the systems components.  
 
Terminal N should be wired to the common of the same source supplying power to terminals E, A, and K.  
All remote wiring should be installed in a clean (no electrical noise) environment. Wire size should be a 
minimum of 24ga. twisted pair to reduce electrical noise (shielded wire is recommended).  For longer runs 

Содержание EngA W-TRAC

Страница 1: ...ORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 4774 Fx 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fx 913 583 1406 1175 TWINNEY DRIVE NE...

Страница 2: ...a safe place The other set is attached to the control panel door and should never be removed Please report any omissions to the national service manager Warning Improper installation adjustment altera...

Страница 3: ...A W TRAC IOM 49 3 of 12 Mar 99 R4...

Страница 4: ...7 TEMPERATURE CONTROL 7 BASE SETPOINT 8 SETPOINT RESET 8 FROST CONTROL 8 EXHAUST AIR RH SENSOR 8 RETURN AIR RH SENSOR 9 BDRH PREDICTED RETURN AIR RELATIVE HUMIDITY 9 WIRING 9 SENSOR TABLE 12 SERVICE N...

Страница 5: ...AC is designed to control only Engineered Air equipment Various upgrades and improvements have been made over time Always include any suffix letters and numbers for troubleshooting and or replacement...

Страница 6: ...d style DC drive motors P2 Wiper output potentiometer legacy for old style DC drive motors P3 High output potentiometer legacy for old style DC drive motors DIP SWITCHES W TRAC configuration options a...

Страница 7: ...y experienced and qualified personnel POT Description DIS CAL Discharge temperature sensor calibration EX CAL Exhaust temperature sensor calibration AMB CAL Ambient outdoor temperature sensor calibrat...

Страница 8: ...put voltage to terminals S and C1 with a setpoint fixed at 66 F Refer to the equipment function page for the design reset range Input Voltage 0 0 2 0 4 0 6 0 8 0 10 0 Discharge Setpoint F C No Resisto...

Страница 9: ...values are expected to be reasonably constant In these cases the W TRAC operates by sensible temperature only When enabled the BDRH pot Building Design Relative Humidity is set according to the expec...

Страница 10: ...ers Refer to the equipment wiring diagram for connection details The following setup parameters are typical Always refer to the equipment function sheet for any changes To ensure proper setup operatio...

Страница 11: ...the temperature at the sensing element Compare these readings to the sensor table values If the resistance is out by more than 16 ohms replace the sensor Measuring a sensor temperature between 60 70...

Страница 12: ...RH SENSOR TABLE Sensor Resistance Chart for TE6000EA3 Table 2 C F Resistance C F Resistance C F Resistance 40 40 602 18 3 65 983 48 9 120 1234 34 4 30 633 20 68 996 54 4 130 1269 28 9 20 665 20 6 69 1...

Отзывы: