background image

A

 

 

W-TRAC

 

 
 

IOM‐49 

                           8 of 12 

Mar 99  R4 

 

 
 

If the outside air temperature is warmer than the exhaust air the W‐TRAC will enter ‘cool mode’ and 
rotate the heat wheel to transfer heat from the outside air to the exhaust. 

 

BASE

 

SETPOINT

 

 
The W‐TRAC is designed to be a discharge air temperature controller.  The base discharge air temperature 
is set from the setpoint control knob located on the face of the W‐TRAC.   
 

SETPOINT

 

RESET

 

 
The base discharge air temperature is often modified from a remote signal to maintain the desired 
temperature of the supplied space.  This is called 

reset

. The W‐TRAC discharge temperature can be reset 

from a variety of sources using a 0‐10 VDC signal. 
 
An offset to the BMS input range can be implemented by adding a 7.5k resistor in series with terminal S. 
The following table describes the change of discharge setpoint from the input voltage (to terminals S + and 
C1 ‐), with a setpoint fixed at 66°F.  Refer to the equipment function page for the design reset range. 
 
 

 

Input Voltage 

 

 

0.0 

2.0 

4.0 

6.0 

8.0 

10.0 

Discharge 
Setpoint (°F/°C) 

No Resistor 

30 / ‐1 

40 / 4 

45 / 7 

52 / 11 

60 / 15 

66 / 19 

7.5k Resistor 

48 / 9 

53 / 12 

56 / 13 

59 / 15 

63 / 17 

66 / 19 

 
 

FROST

 

CONTROL

 

 
Frost should not be allowed to build up on the wheel.  It is necessary to reduce the amount of heat 
recovered when the outside temperature is below the freezing point (0°C / 32°F) and the exhaust leaving 
temperature falls to a point that frost can begin to form.  Frost may damage the wheel and reduce airflow. 
 
Operating the heat wheel close to the frost threshold temperature will provide maximum energy recovery.  
There are 3 different methods of providing frost control, all of which reduce the heat wheel rotation 
speed. 

 

EXHAUST

 

AIR

 

RH%

 

SENSOR

 

 
This method of control requires a humidity sensor connected across terminals EXH and C2.  DIP 1 and 3 
must be OFF, DIP 2 must be ON.  The sensor is installed in the exhaust air section, just after the heat 
wheel. 
 

Содержание EngA W-TRAC

Страница 1: ...ORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 4774 Fx 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fx 913 583 1406 1175 TWINNEY DRIVE NE...

Страница 2: ...a safe place The other set is attached to the control panel door and should never be removed Please report any omissions to the national service manager Warning Improper installation adjustment altera...

Страница 3: ...A W TRAC IOM 49 3 of 12 Mar 99 R4...

Страница 4: ...7 TEMPERATURE CONTROL 7 BASE SETPOINT 8 SETPOINT RESET 8 FROST CONTROL 8 EXHAUST AIR RH SENSOR 8 RETURN AIR RH SENSOR 9 BDRH PREDICTED RETURN AIR RELATIVE HUMIDITY 9 WIRING 9 SENSOR TABLE 12 SERVICE N...

Страница 5: ...AC is designed to control only Engineered Air equipment Various upgrades and improvements have been made over time Always include any suffix letters and numbers for troubleshooting and or replacement...

Страница 6: ...d style DC drive motors P2 Wiper output potentiometer legacy for old style DC drive motors P3 High output potentiometer legacy for old style DC drive motors DIP SWITCHES W TRAC configuration options a...

Страница 7: ...y experienced and qualified personnel POT Description DIS CAL Discharge temperature sensor calibration EX CAL Exhaust temperature sensor calibration AMB CAL Ambient outdoor temperature sensor calibrat...

Страница 8: ...put voltage to terminals S and C1 with a setpoint fixed at 66 F Refer to the equipment function page for the design reset range Input Voltage 0 0 2 0 4 0 6 0 8 0 10 0 Discharge Setpoint F C No Resisto...

Страница 9: ...values are expected to be reasonably constant In these cases the W TRAC operates by sensible temperature only When enabled the BDRH pot Building Design Relative Humidity is set according to the expec...

Страница 10: ...ers Refer to the equipment wiring diagram for connection details The following setup parameters are typical Always refer to the equipment function sheet for any changes To ensure proper setup operatio...

Страница 11: ...the temperature at the sensing element Compare these readings to the sensor table values If the resistance is out by more than 16 ohms replace the sensor Measuring a sensor temperature between 60 70...

Страница 12: ...RH SENSOR TABLE Sensor Resistance Chart for TE6000EA3 Table 2 C F Resistance C F Resistance C F Resistance 40 40 602 18 3 65 983 48 9 120 1234 34 4 30 633 20 68 996 54 4 130 1269 28 9 20 665 20 6 69 1...

Отзывы: