background image

 

M-TRAC1

 

 

IOM-55 

 

May 2019 

 

 

ADJUSTMENT POTS 

 
There are a number of setting and calibration potentiometers (POT’s) located on the face of the 
M-TRAC1.  Modifications to these should only be performed by experienced and qualified 
personnel. 
 

TABLE 4 

POT 

Description 

SP LMT 

Limits the maximum discharge temperature set point. 

CAL DTEMP 

Discharge air sensor temperature calibration. 

SP CAL 

Setpoint dial calibration. 

MIN FIRE 

Adjusts the minimum valve output for low fire. 

SERVICE POT 

Manually sets burner firing rate for service. Located just above the centre.  
When the service switch is on, this POT can be used to adjust the 
modulating gas valve from low to high fire.  When the service DIP switch is 
on, light ‘D’ blinks irregularly. 

2-10 Vdc 
RESET RATIO 

Sets the reset temperature range.  This adjusts the amount of reset range 
the 2-10 Vdc room thermostat will have. This allows an adjustment band 
between 5

°

F and 50°F (3°C and 28°C). 

PROFILE 
VELOCITY 

Allows a narrow adjustment for Profile pressure set point. 

 
MULTIMETER TEST POINTS 

 
The M-TRAC1 has readout test points for discharge air temperature, discharge set point and 
profile plate velocity status.  

Temperature readings are indicated by Vdc referenced to ground.

 

 

MAXIMUM DISCHARGE SET POINT LIMIT SETUP (SP LMT)  

 
Regulations, design or authorities having jurisdiction may limit the maximum discharge air 
temperature the appliance is allowed to reach.  This may be set by the potentiometer SP LMT, 
which is located below and to the right of the M-TRAC1 discharge set point knob.  Vdc readout 
= °C / 10.  See Table 5. 

 

CALCULATED SETPOINT (SPC) 

 

The SPC measurement point is located just below the M-TRAC1 set point knob.  This 
temperature is the current operating set point after all applicable temperature resets have 
been applied to primary or base set point.  Vdc readout = °C / 10.  See Table 5. 
 
 
 
 
 

Содержание EngA M-TRAC1

Страница 1: ...ANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 2590 Fax 888 364 2727 32050 W 83 rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fax 913 583 1406 1175 TWINNEY DRIVE NEWM...

Страница 2: ...nvelope which also contains the Operation Installation and Maintenance manual s This package is for copying then should either be returned to the appliance or stored in a safe place The other set is a...

Страница 3: ...A M TRAC1 IOM 55 May 2019 3...

Страница 4: ...AIR SENSOR 10 LOW LIMIT 10 DAMPER CONTROL 11 BLOWER CONTROL 11 BURNER CONTROL 11 PROFILE PLATE VELOCITY SENSING SYSTEM 12 TEMPERATURE RESET 12 MAKE BREAK THERMOSTAT 12 2 10 Vdc SIGNAL 12 OPERATION 13...

Страница 5: ...Engineered Air equipment Various upgrades and improvements have been made over time Always include any suffix letters and numbers for troubleshooting and or replacement All M TRAC1 models are backward...

Страница 6: ...RS Return from the remote set point POT S Setpoint enable 2 to 10 Vdc input PF Not used H 24 Vac hot N 24 Vac neutral FS Fan switch input HS Heat switch input LMT Input from safety limit high limit VN...

Страница 7: ...Valve Light Off Position 4 Disable Open Sensor Checking See Discharge Air Setpoint 3 Disable Low Limit See Low Limit 2 Alarm contact to be used for reverse interlock See Reverse Interlock 1 2 10 Vdc...

Страница 8: ...set range the 2 10 Vdc room thermostat will have This allows an adjustment band between 5 F and 50 F 3 C and 28 C PROFILE VELOCITY Allows a narrow adjustment for Profile pressure set point MULTIMETER...

Страница 9: ...ity is optimum the reading is 6 Vdc For other voltage readings see Table 6 Note that if the airflow is reduced below safe operating conditions there are delays built into the M TRAC1 that will shut of...

Страница 10: ...in equipment with temperature rise over 100 F 55 C or with dual fans In most applications the discharge air sensor s is located in the supply blower outlet The discharge air sensor also serves as a lo...

Страница 11: ...um airflow is defined as 60 of required airflow Airflow priority is defined as 40 of required airflow TABLE 7 Priority Level Status Comfort Air Flow Heat switch off Low airflow Lock out in 50 seconds...

Страница 12: ...e contact or space mounted single stage thermostat with the second upper level adjustable from 75 24 C to 170 F 77 C by the SP LMT POT 2 10 Vdc SIGNAL The set point can be adjusted linearly upwards fr...

Страница 13: ...the burner at approximately 40 of full fire non adjustable The positioning time delay allows the modulating valve actuator time to reach the correct light off position before an ignition attempt is m...

Страница 14: ...emains stable Due to the nature of direct fired appliance the air temperature leaving the supply blower is often very stratified It is important to understand that the supply blower does not significa...

Страница 15: ...step 6 Adjust SP LMT until the voltage reading is the same as was recorded in step 5 SERVICE SERVICE MODE Placing the M TRAC1 into service mode allows for direct control of the burner firing rate Onc...

Страница 16: ...current when open BMS SENSOR LOCATION The Engineered Air sensor must be calibrated to match its operation with the Engineered Air control Do not calibrate it to match BMS readout if one exists If ther...

Страница 17: ...flow is below 40 C Slow Low air flow Sensed air flow is below 60 C On High air flow Sensed air flow is over 120 D Fast Ignition failure E Irregular Open discharge air sensor Sensor resistance should...

Страница 18: ...enable damper actuator Dampers opening Confirm output voltage at terminal DM Check wiring connections to damper actuator Confirm damper actuator is operational Check damper assembly is free to move N...

Страница 19: ...e DIP 6 on or delay to set modulating valve to ignition position No Yes Yes Yes Yes No No No FR and CFR contacts close PV1 and PV2 contacts close Ignition control enabled Ignition sequence Ignition co...

Отзывы: