M-TRAC1

 

 

IOM-55 

 

May 2019 

 

10 

(reason for the lockout) will be lost.  When power is resumed the M-TRAC1 will remain locked 
out, but only green LED flashing irregularly.   
 

CONTROL 

 
 

SYSTEM TIMING  

 
Damper opening delay:  Depends on type of damper actuator used. 
Blower startup:  54 seconds after terminal FS is energized. 
Low Limit bypass:  4.5 minutes from initial startup, 50 seconds nuisance timer. 
Trial for ignition:  30 sec. 
 

DISCHARGE AIR SETPOINT 

 
The M-TRAC1 is a discharge air temperature controller with a built in face mounted set point 
knob (that is activated by connecting terminal S to SP).  Optionally, the M-TRAC1 is available 
with a remote set point, with varying set point ranges.  When a remote setpoint is provided, the 
M-TRAC1 face mounted set point will have no effect. 
 
Additional methods of resetting the discharge air temperature setpoint may be used.  Refer to 
the unit function and electrical drawing. 
 

DISCHARGE AIR SENSOR 

 
The M-TRAC1 is designed to use either a single or dual discharge sensors, wired in series.  Dual 
sensors are always used in equipment with temperature rise over 100˚F (55°C) or with dual 
fans.  In most applications the discharge air sensor(s) is located in the supply blower outlet. 
 
The discharge air sensor also serves as a low limit (or freeze protection) sensor.  The part 
number of the sensor is noted on the electrical drawing. 
 
The M-TRAC1 automatically checks the discharge air sensor(s). If the M-TRAC1 reads an open 
sensor it will disable temperature control and reduce the firing rate to low fire, then shutdown 
the appliance.  Open sensor checking may be disabled by switching on DIP switch #4.   
 

LOW LIMIT  

 
The M-TRAC1 control is typically configured so that the discharge air temperature sensor also 
performs the function of a low limit or freeze stat.  If DIP switch 3 is ‘off’ the low limit function 
is enabled.  If the discharge temperature falls below 40˚F (4°C) the appliance will shut down and 
the LED for low discharge temperature will begin flashing.  On initial startup the M-TRAC1 will 
internally bypass the low limit for 3 minutes.  After this time, the low limit discharge 
temperature must be below the low limit setpoint (40°F / 4°C) for 50 seconds before the  
M-TRAC1 will shut the appliance off.   
If DIP switch 3 is ‘on’, the low limit safety function is disabled. 

Содержание EngA M-TRAC1

Страница 1: ...ANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 2590 Fax 888 364 2727 32050 W 83 rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fax 913 583 1406 1175 TWINNEY DRIVE NEWM...

Страница 2: ...nvelope which also contains the Operation Installation and Maintenance manual s This package is for copying then should either be returned to the appliance or stored in a safe place The other set is a...

Страница 3: ...A M TRAC1 IOM 55 May 2019 3...

Страница 4: ...AIR SENSOR 10 LOW LIMIT 10 DAMPER CONTROL 11 BLOWER CONTROL 11 BURNER CONTROL 11 PROFILE PLATE VELOCITY SENSING SYSTEM 12 TEMPERATURE RESET 12 MAKE BREAK THERMOSTAT 12 2 10 Vdc SIGNAL 12 OPERATION 13...

Страница 5: ...Engineered Air equipment Various upgrades and improvements have been made over time Always include any suffix letters and numbers for troubleshooting and or replacement All M TRAC1 models are backward...

Страница 6: ...RS Return from the remote set point POT S Setpoint enable 2 to 10 Vdc input PF Not used H 24 Vac hot N 24 Vac neutral FS Fan switch input HS Heat switch input LMT Input from safety limit high limit VN...

Страница 7: ...Valve Light Off Position 4 Disable Open Sensor Checking See Discharge Air Setpoint 3 Disable Low Limit See Low Limit 2 Alarm contact to be used for reverse interlock See Reverse Interlock 1 2 10 Vdc...

Страница 8: ...set range the 2 10 Vdc room thermostat will have This allows an adjustment band between 5 F and 50 F 3 C and 28 C PROFILE VELOCITY Allows a narrow adjustment for Profile pressure set point MULTIMETER...

Страница 9: ...ity is optimum the reading is 6 Vdc For other voltage readings see Table 6 Note that if the airflow is reduced below safe operating conditions there are delays built into the M TRAC1 that will shut of...

Страница 10: ...in equipment with temperature rise over 100 F 55 C or with dual fans In most applications the discharge air sensor s is located in the supply blower outlet The discharge air sensor also serves as a lo...

Страница 11: ...um airflow is defined as 60 of required airflow Airflow priority is defined as 40 of required airflow TABLE 7 Priority Level Status Comfort Air Flow Heat switch off Low airflow Lock out in 50 seconds...

Страница 12: ...e contact or space mounted single stage thermostat with the second upper level adjustable from 75 24 C to 170 F 77 C by the SP LMT POT 2 10 Vdc SIGNAL The set point can be adjusted linearly upwards fr...

Страница 13: ...the burner at approximately 40 of full fire non adjustable The positioning time delay allows the modulating valve actuator time to reach the correct light off position before an ignition attempt is m...

Страница 14: ...emains stable Due to the nature of direct fired appliance the air temperature leaving the supply blower is often very stratified It is important to understand that the supply blower does not significa...

Страница 15: ...step 6 Adjust SP LMT until the voltage reading is the same as was recorded in step 5 SERVICE SERVICE MODE Placing the M TRAC1 into service mode allows for direct control of the burner firing rate Onc...

Страница 16: ...current when open BMS SENSOR LOCATION The Engineered Air sensor must be calibrated to match its operation with the Engineered Air control Do not calibrate it to match BMS readout if one exists If ther...

Страница 17: ...flow is below 40 C Slow Low air flow Sensed air flow is below 60 C On High air flow Sensed air flow is over 120 D Fast Ignition failure E Irregular Open discharge air sensor Sensor resistance should...

Страница 18: ...enable damper actuator Dampers opening Confirm output voltage at terminal DM Check wiring connections to damper actuator Confirm damper actuator is operational Check damper assembly is free to move N...

Страница 19: ...e DIP 6 on or delay to set modulating valve to ignition position No Yes Yes Yes Yes No No No FR and CFR contacts close PV1 and PV2 contacts close Ignition control enabled Ignition sequence Ignition co...

Отзывы: