Product Specification Manual - Destination 1.9
ENGLISH
2. Clearances to Combustible Material
When the insert is installed so that its surfaces are at or beyond the minimum clearances
specified, combustible surfaces will not overheat under normal and even abnormal operating
conditions.
NO PART OF THE INSERT MAY BE LOCATED CLOSER TO THE COMBUSTIBLE THAN THE
MINIMUM CLEARANCE FIGURES GIVEN.
2.1 Minimum Masonry Opening and Clearances to Combustibles
COMBUSTIBLE MANTEL SHELF
COMBUSTIBLE
TOP SURROUND
CO
M
BU
ST
IB
LE
SI
DE
S
URR
O
UN
D
AD
JA
CE
NT
S
ID
E
W
AL
L
FLOOR PROTECTION
I
Q
F
K
L
O
P
R
J
Figure 7 : Ouverture de l'âtre et dégagements aux combustibles
MINIMUM CLEARANCES
F
16" (406 mm)
I
34" (864 mm)
Q
72" (183 cm)
MAXIMUM THICKNESS
O
3" (76 mm)
P
1.5" (38 mm)
R
12" (305 mm)
MINIMUM MASONRY
OPENING
J
19" (483 mm)
K
14
25" (635 mm)
L
15 ½" (394 mm)
FACADE
CLEARANCES
From combustible
side surround
1" (25 mm)
From combustible top
surround
1" (25 mm)
14
If a fresh air intake is required, it is recommended to add at least 4" to the width of the minimum opening of the hearth.