14
3916010 06.16
Fig. 13
5. STARTUP AND CONFIGURATION
5.1 GENERAL
Prior to startup please review the paragraph below titled
Dipswitch settings.
Dipwitch settings
Prior to setting the system, check to see if the dipswitch
settings are as required:
• Default factory setting: All OFF
• If the factory setting must be changed, remove the black
cover plate to gain access to the dipswitches
(see Fig 13-A):
1. Remove the potentiometer dial.
2. Remove the (4) flathead screws and lift the top plate off
the board.
3. Change the dipswitch settings.
DIP SWITCH
NAME
OFF
ON
1
MANUAL
RESET
Automatic reset at power
failure or insufficient
pressure
Manual reset at power
failure or insufficient
pressure
2
POST
PURGE
No post-purge
3 minutes of post-
purge
3*
PDS
CHECK*
No monitoring to see
if the PDS was in NC
position prior to start
The PDS must be in
NC position prior to
start
*Always OFF if the Proven Pressure Switch (PDS) is not connected.