8
3002600 08.17
3.3 DRAIN INSTALLATION
Install the provided drain if the IPVB is mounted in position B.
The drain should be installed near the outlet of the fan and
oriented so it points toward the ground.
To install the drain:
1. Use the drain as a template to drill (4) 1/8" holes in each
corner.
2. Use the (4) provided rivets to fasten the drain to the fan
housing.
3. Using the fitting as a guide, drill a 1/2" hole through the
housing to open the drain.
B
3.4 MOUNTING OF POWER VENTER
The IPVB has (4) 0.413" diameter mounting holes on each
end of the fan. Threaded rod or steel hangers should run
through these holes to hang the fan from the ceiling or other
support.
Ø0.41"
Ø0.41"
3.5 LOCATION/CONNECTIONS
Follow the recommendations by the vent or stack
manufacturer. The power venter should be located at least (3)
times the vent diameter from any elbow or tee.
A set of v-bands are shipped with the fan for connection to
the stack.
3 x D
D
Fig 3
Fig 4
Fig 5