2.  SPECIFICATIONS

2.1 DIMENSIONS & CAPACITIES 

IPVB 

400

1000 

2000 

5000 

0.0 

1.0 

 

0.5 

2.0 

 

1.5 

3.0 

 

2.5 

4.0 

 

3.5 

5.0 

 

4.5 

3000

4000

P

t

 (inW.C.) 

Volume (cfm) 

6000 

IPVB 500

IPVB 35

0

IPVB 30

0

Capacity

NOTE:  
The capacity data above is tested in accordance with ISO 
Standard 5801-Industial Fans Performance Testing Using 
Standardized Airways.

Removal of drive unit

Fan without drive unit

Model

IPVB 300 IPVB 350 IPVB 400 IPVB 500

Fan Type

Centrifugal Impeller (B-wheel)

Motor Type

TEFC

Voltage

VAC

1 x 120

3 x 200-240 / 3 x 440-480

Amperage

Amps

5.8

2.6 / 1.5

5.5 / 2.9

7.8 4.1

Motor

Output HP

0.5

1.0

2.0

3.0

kW

0.35

0.75

1.5

2.2

Max. RPM

1600

1740

Duct Connection

in

12

14

16

20

(Nominal)

mm

300

350

400

500

Dimensions

A

in

19.3

22.4

26.4

29.5

mm

490

569

671

749

B

in

13.0

14.6

17.0

21.3

mm

330

371

432

541

C

in

13.9

15.5

17.8

22.1

mm

353

394

452

561

D

in

12.1

14.0

16.0

20

mm

306

356

406

508

E

in

11.1

12.7

14.6

16.2

mm

282

322

370

411

F

in

6.9

7.8

8.9

11.1

mm

175

198

226

282

G

in

15.8

15.8

16.2

20.1

mm

401

401

411

511jj

H

in

21.6

24.6

26.3

30.0

mm

549

625

668

762

J

in

2.5

2.5

2.6

2.7

mm

64

64

66

69

L

in

47.1

51.2

56.8

66.9

mm

1199

1300

1443

1699

W

in

22.2

25.3

29.2

32.4

mm

564

643

742

823

Weight

lbs

75

94

128

182

kg

34

42.5

58

82.5

Max. Temperature

575°F (302°C) Continous

Specifications

Содержание IPVB 300

Страница 1: ...rkway Alpharetta GA 30004 USA P 770 587 3238 F 770 587 4731 T 800 255 2923 info enervex com www enervex com 3002600 08 17 Installation Operating Manual ENERVEX IPVB 300 500 INLINE POWER VENTER READ AN...

Страница 2: ...ed by this manual Please refer to these component s individual manuals TO REDUCE THE RISK OF FIRE ELECTRICAL SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING 1 Use this unit in the manner intended by...

Страница 3: ...Horizontal Installation 9 4 ELECTRICAL INSTALLATION 4 1 General 10 4 2 Wiring Diagram IPVB 300 10 4 3 Wiring Diagram IPVB 350 500 11 4 4 Installing a Proven Draft Switch 12 4 5 Installation of Stack...

Страница 4: ...hich is mounted outside the air stream The design is a Type B Spark Resistant Construction The motor and impeller is a complete assembly drive unit that can be removed from the fan housing without rem...

Страница 5: ...All single phase fans ae shipped with a capacitor and junction box connected via conduit The capacitor is located INSIDE the junction box Please do not discard 1 4 WARRANTY ENERVEX products are warran...

Страница 6: ...Amps 5 8 2 6 1 5 5 5 2 9 7 8 4 1 Motor Output HP 0 5 1 0 2 0 3 0 kW 0 35 0 75 1 5 2 2 Max RPM 1600 1740 Duct Connection in 12 14 16 20 Nominal mm 300 350 400 500 Dimensions A in 19 3 22 4 26 4 29 5 mm...

Страница 7: ...e it discharges through a wall A drain is provided with the IPVB to be installed by the user The IPVB is for indoor and outdoor installation Unless installed adjacent to the wall it is discharging thr...

Страница 8: ...fitting as a guide drill a 1 2 hole through the housing to open the drain B 3 4 MOUNTING OF POWER VENTER The IPVB has 4 0 413 diameter mounting holes on each end of the fan Threaded rod or steel hang...

Страница 9: ...ONTAL INSTALLATION To mount the IPVB horizontally suspend the power venter with threaded rod or steel hangers It may be necessary to cross brace the fan from end to end to prevent side sway Ensure the...

Страница 10: ...ectrical metallic tubing or be otherwise suitably protected from physical damage IPVB models operate at different voltages please pay attention to the wiring details IPVB 300 operates at 1x120VAC whil...

Страница 11: ...the motor junction box The motor wiring terminals shown in Fig 9 shows default jumper positions for 3x440 480VAC operation If the application requires 3x208 230VAC operation the jumper positions must...

Страница 12: ...s and Capacities The power venter is equipped with a variable speed motor Fig 11 below shows a typical wiring diagram utilizing a Variable Frequency Drive adjusting the speed is possible If it is not...

Страница 13: ...let of the fan the rotation of the impeller should be clockwise as shown in Fig 13 Correct rotation direction is also indicated by an arrow on the motor end cover There are holes in the end cover that...

Страница 14: ...ot apply to IPVB 300 All IPVB fans run in a clockwise direction when viewed from the fanoutlet or when looking down at the motor 4 Switching any two phases between the fan and the power source VFD is...

Страница 15: ...15 below follow these steps to open the venter so it can be cleaned and inspected 1 Remove the four hex nuts holding the motor mounting plate to the housing 2 Motor and impeller assembly can be lifte...

Страница 16: ...nce in the power to the fan is reversed Swap two phases in the junction box The fan is vibrating vigorously Foreign matter is stuck in the impeller A ball bearing is damaged A balancing weight has fal...

Страница 17: ...17 3002600 08 17 Notes...

Страница 18: ...18 3002600 08 17 Notes...

Страница 19: ...19 3002600 08 17 Notes...

Страница 20: ...ENERVEX Inc 1685 Bluegrass Lakes Parkway Alpharetta GA 30004 USA P 770 587 3238 F 770 587 4731 T 800 255 2923 info enervex com www enervex com 3002600 08 17...

Отзывы: