79
Installation instructions for professionals
TECHNICAL SPECIFICATIONS OF THE UNIT
connection cable with plug
Width
580 mm
Depth
500 mm
Height
490 mm
Weight
45 kg
Duct connection (duct size)
Ø 160 mm
Duct connection (duct size) CHC
Ø 125 mm
Range hood connection (duct size) CHC
Ø 100 mm
Fans
supply 118 W, 1.0 A; exhaust 118 W, 1.0 A
Heat exchanger motor with thermal protection
5 W, 0.04 A
Power of electric post-heating coil in E-models
400 W/230 V, 1~/50 Hz/1.74 A
Power of electric pre-heating coil in Arctic models
800 W/230 V, 1~/50 Hz/3.5 A
Input power, E-model (post-heating coil)
641 W/230 V, 1~/50 Hz/3.78 A
Input power E Arctic model (post-heating and pre-heating coil)
1441 W/230 V, 1~/50 Hz/7.26 A
Circuit breaker
B10 A
Mains supply
230 V, 1~/50 Hz/10 A
motherboard
type plate
inlets for external sensors
heat exchanger
heat exchanger’s drive belt
heat exchanger’s spare belt
supply fan
extract fan
extract filter
inlet filter
condensate connection
DN 20 X 12mm
Right-handed CHC
Содержание Salla eWind
Страница 12: ...12 9 11 10 Wifi moduulin asennus 1 2 A B A 3 4...
Страница 23: ...23 Ammattilaisen asennusohje...
Страница 26: ...26 Salla eWind Installationsanvisningar f r ventilationsaggregat Svenska...
Страница 36: ...36 9 11 10 Installation av Wifi modulen 1 2 A B A 3 4...
Страница 47: ...47 Installationsanvisningar f r yrkesfolk...
Страница 50: ...50 Installeringsinstruksjoner for ventilasjonsenheten Norsk Salla eWind...
Страница 60: ...60 9 11 10 Installasjon av Wifi modulen 1 2 A B A 3 4...
Страница 71: ...71 Installasjonsinstrukser for fagfolk...
Страница 74: ...74 Salla eWind Installation instructions for the ventilation unit English...
Страница 84: ...84 9 11 10 Installation of the Wifi module 1 2 A B A 3 4...
Страница 95: ...95 Installation instructions for professionals...
Страница 104: ...104 Anslutningar Elscheman F rkortning F rg BK SVART BN BRUN RD R D OG ORANGE YE GUL GN GR N BU BL GY GR WH VIT...