Commissioning
P.
19 of 349
Reset - factory settings
Because this interface could be sometimes be in a locked state, it should be reset once. The
interface is accessed and activated only after the transfer and the subsequent start of an application
program (in case of a not duly executed separation of a connection to the ets or an access via
another LAN subscriber). The Enertex
®
EibPC uses the so-called tunneling mode of the IP interface.
During the power up the green Info LED is on continuously. Then the Info LED is blinking every
second for 3 seconds. Only during this 3s phase the reset button is active.
By pressing the reset the following is triggered:
1.
Reset to factory settings of the network configurations
2.
Deletion of the application program
3.
Deletion the data of the solar altitude
The pin-out of the RS-232 interface of the Enertex
®
EibPC corresponds to the standard EIA-232.
Use the supplied cable for the communication of the Enertex
®
EibPC with the KNX
TM
RS-232
interface.
If you have a Patch 1.101 installed Enertex
®
EibPC will boot in less then 40 seconds. Otherwise the
boot will last for about 4 minutes.
A Patch-Updat will also boot in less then 40 seconds.