6
Enertech Global
HP IOM, Rev. B
⚠
CAUTION
⚠
All GEOTHERMAL equipment is designed for indoor
installation only. DO NOT install or store unit in a corrosive
environment or in a location where temperature and
humidity are subject to extremes. Equipment is not
certified for outdoor applications. Such installation will
void all warranties.
⚠
WARNING
⚠
Failure to follow this caution may result in personal injury.
Use care and wear appropriate PROTECTIVE clothing,
safety glasses and protective gloves when servicing unit
and handling parts.
⚠
CAUTION
⚠
Before drilling or driving any screws into cabinet, check
to be sure the screw will not hit any internal parts or
refrigerant lines�
Section 2: Installation Introduction
Components
Master Contactor: Energizes Compressor and optional
Hydronic Pump and/or Desuperheater pump package.
Logic Board: Logic Board operates the compressor and
protects unit by locking out when safety switches are engaged.
It also provides fault indicator(s).
Terminal Strip: Provides connection to the thermostat or other
accessories to the low voltage circuit.
Transformer: Converts incoming (source) voltage to 24V AC.
Low Voltage Breaker: Attached directly to transformer,
protects the transformer and low voltage circuit.
High Pressure Switch: Protects the refrigerant system from
high refrigerant pressure, by locking unit out if pressure
exceeds setting.
Low Pressure Switch: Protects the refrigerant system from low
suction pressure, if suction pressure falls below setting.
Shipping Bolts: This unit is equipped with the new
COMPRESSOR ISOLATION feature. Do not loosen or remove
the bolts.
Consumer Instructions
Dealer should instruct the consumer in proper operation,
maintenance, filter replacements, thermostat and indicator
lights. Also provide the consumer with the manufacturer’s
Owner’s Manual for the equipment being installed.
Enertech Global D-I-Y Policy: Enertech Global’s geothermal
heat pumps and system installations may include electrical,
refrigerant and/or water connections. Federal, state and
local codes and regulations apply to various aspects of the
installation. Improperly installed equipment can lead to
equipment failure and health/safety concerns. For these
reasons, only qualified technicians should install a Enertech
Global built geothermal system.
Because of the importance of proper installation, Enertech
Global does not sell equipment direct to homeowners.
Internet websites and HVAC outlets may allow for purchases
directly by homeowners and do-it-yourselfers, but Enertech
Global offers no warranty on equipment that is purchased via
the internet or installed by persons without proper training.
Enertech Global has set forth this policy to ensure installations
of Enertech Global geothermal systems are done safely and
properly. The use of well-trained, qualified technicians helps
ensure that your system provides many years of comfort and
savings.
Equipment Installation
Special care should be taken in locating the unit. All units
should be placed on a formed plastic air pad, or a high
density, closed cell polystyrene pad slightly larger than the
base of the unit. All units should be located in an indoor area
were the ambient temperature will remain above 55°F and
should be located in a way that piping and ductwork or other
permanently installed fixtures do not have to be removed for
servicing and filter replacement.
Electrical
All wiring, line and low voltage, should comply with the
manufacturer's recommendations, The National Electrical
Code, and all local codes and ordinances�
Thermostats should be installed approximately 54 inches off
the floor on an inside wall in the return air pattern and where
they are not in direct sunlight at anytime.
Loop Pumping Modules must be wired to the heat pump’s
electric control box. A special entrance knockout is provided
below the thermostat entrance knockout. A pump module
connection block, connected to the master contactor, and
circuit breaker is provided to connect the Pump Module
wiring.