01. GENERAL
Manual
- The contents of this manual are to be observed by all who work for any
reason on the unit and its appertaining system parts.
- This manual is intended especially for authorised personnel.
- This manual is to be regarded as part of the burner and shall always
be available near the place of installation.
Safety directions
The electrical installation shall be made according to valid regulations for
heavy current and in a professional way, so that the risk of leaking oil, fire
or personal injury is avoided.
Care should be taken by the installer to ensure that no electrical cables or
fuel/gas pipes are trapped or damaged during installation or service/
maintenance.
Condensation in chimney
A modern burner works with less air surplus and often with a smaller nozzle
than older models. This improves the efficiency but increases also the risk
of condensation in the chimney. The risk is greater if the cross sectional
area of the chimney flue is too big. Temperature of the flue gases should be
higher than 60°C measured 0.5 m from the top of the chimney.
Setting the burner
A flue-gas analysis and measuring of the temperature should be done to
facilitate a correct setting. There is otherwise a risk of soot, poor efficiency
or condensation in the chimney.