9
171 535 13 06-01
1(3)
02. TECHNICAL DATA
Type designation B55-2H/B55-2/B55-2R/B55-3R/B65-2H/B65-2/B65-2R/B65-3R
Dimensions
Length of
Flange
Burner tube
Burner tube Length of
Flange
Burner tube Burner tube
burner tube Measure B Measure C
Measure D burner tube Measure B Measure C Measure D
B55
B55
B55
B55
B65
B65
B65
B65
Standard 1
303
273
160
155
288
258
200
155
Standard 2
403
373
160
155
388
358
200
155
Standard 3
503
473
160
155
488
458
200
155
Output range and nozzles recommended
Oil capacity
Output
Recommended nozzle
Recommended
kg/h
kW
Mcal/h
Angle
Danfoss
Pump pressure
B55-2H, B55-2, B55-2R
14-67
166-795
143-685
45°-60°
S, B
14 bar
B55-3R
14-64
166-759
143-654
45°-60°
S, B
14 bar
B65-2H, B65-2, B65-2R
24-99
285-1174
246-1012
45°-60°
S, B
14 bar
B65-3R
24-99
285-1174
246-1012
45°-60°
S, B
14 bar
The net calorific value of 11,86 kWh/kg for light oil has been used.
Recommended nozzle and pressure
Because of the different boiler types, combustion chamber geometries
and combustion chamber loads that exist, it is not possible to specify a
given spray angle or spray pattern.It should be noted that the spray angle
and spray pattern will vary depending on the pump pressure.
Nozzle
45°S Danfoss
45°B Danfoss
60°S Danfoss
60°B Danfoss
Pump pressure
14 bar (12 - 16 bar)
On burners equipped with hydraulic air control or optimization the oil pressure
should not be less than 14 bar.
B
C
405
400
321
610
595
290
D