Function Danfoss BFP21L5

When the oil pump is started, oil is 

drawn from the suction connection 

(S) through the ilter (H) to the suction 

side of the gear wheel (C).
The gear wheel then pumps oil to the 
pressure side and the oil is put under 
pressure.
The pressure is controlled and kept 
constant at the set value by the regula-
ting valve (P

1

) with the diaphragm (D).

The regulating valve (P

1

) distributes 

the oil quantity supplied by the gear 
set (C) between the nozzle port (E) 
and the return side of the pump (R).
The oil quantity utilized is determined 
by the set pressure on the regulating 
valve (P

1

) and the size of the oil nozzle 

in the nozzle line.
The valve (P

1

) functions in the following 

way:

-  When  the  opening  pressure  has  

  been reached, the passage to the 
  return side opens.

- The diaphragm and the spring 

 

  keep the pump pressure constant 
  at set value.
-  If the pump is overloaded, i.e If you 
  try to get out more oil than the gear 
  set can supply under existing circum- 
  stances, the oil pressure falls below the 
  set value  and the valve closes against 

171 505 10  10-01

Replacement of cartridge ilter

Mounting/dismounting return plug

How to remove cartridge ilter

from plug

Unscrew  the  cartridge  ilter  plug  in 

the cover by means of a 4 mm allen 

key and withdraw the cartridge ilter. If 

necessary, put a screwdriver between 

the cartridge ilter and the plug and 

turn the cartridge ilter carefully until 

it comes off. Reject the cartridge ilter 

and replace it by a new one. Press it 
on to the plug. Ensure that the

O-ring is not damaged. Then it the 

new cartridge ilter to the pump.

One pipe system

Two pipe system

R

S

E

NC

A

G

H

V

P

1

P

D

C

INSTRUCTIONS PUMP TYPE DANFOSS BFP21L5

  the return side (R) by means of the 
  diaphragm (D) and goes into starting 
 position.
This can be remedied by:
-  Reducing the pump pressure.
-  Reducing the oil quantity supplied 
  by using a smaller nozzle.
-  Using a pump with a larger capacity.

Содержание Bentone B40 CN

Страница 1: ...Providing sustainable energy solutions worldwide 178 032 53 2 2016 07 08 Installation and maintenance instruction B40 CN...

Страница 2: ......

Страница 3: ...y 5 Ignition cable 6 Ignition transformer 7 Photo cell 8 Control box 9 Reset button 10 Cover inspection glass 11 Fan wheel 12 Motor 13 Nozzle assembly adjustment 14 Blast tube 15 Air adjustment 16 Air...

Страница 4: ...deinite spray angle or spray pattern Recommended nozzle Output range and nozzles recommended The net caloriic value of 11 86 kWh kg for light oil has been used Burner tube Length of burner tube Measu...

Страница 5: ...s fol lows Increase the nozzle assembly adjustment somewhat The CO2 con tent and consequently the air volume will then be reduced GENERAL INSTRUCTIONS Condensation in chimney A modern burner works wit...

Страница 6: ...ch off power at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A Service of burner head 1 Loosenorswingouttheburner from the boiler 2...

Страница 7: ...l burner control A2 Twin thermostat F1 Fuse max 10A H1 Alarm lamp H2 Signal lamp optional M1 Burner motor P1 Time meter optional R1 Photoresistor S3 Main switch T1 Ignition transformer Y1 Solenoid val...

Страница 8: ...e burner will make an attempt to re start 3 4 Operating position If the burner operation is interrupted by means of the main switch or the thermostat a new start takes place when the conditions in acc...

Страница 9: ...blesapplytoastandardfueloilof normal commercial quality according tocurrentstandards Oncommissioning with an empty tube system the oil pump should not be run without oil for more than 5 min a conditio...

Страница 10: ...f the pump is overloaded i e If you try to get out more oil than the gear setcansupplyunderexistingcircum stances the oilpressurefallsbelowthe setvalue andthevalveclosesagainst 171 505 10 10 01 Replac...

Страница 11: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Страница 12: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Страница 13: ...f magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocel...

Страница 14: ......

Страница 15: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: