INSTRUCTIONS PUMP TYPE DANFOSS BFP 21 L5

Components

1  Nozzle port G1/8"

2. Pressure gauge port G1/8"

3.  Pressure adjustment, 4 mm allen key

4. Cartridge ilter 

5. Vacuum gauge port G1/8"

6. Return line G¼"

7. Suction line G¼"

8. Return plug

9. Pressure gauge port G 1/8"

Technical data

Viscosity range: 

1,8-12,0 mm

2

/s

Pressure range: 

7-15 bar

Rated voltage of coil: 

220/240V

 

50/60 Hz

Oil temperature: 

-10 to +70°C

Suction line tables

The suction line tables consist of 
theoretically calculated values where 
the pipe dimensions and oil velocity 
have been matched so that turbulences 
will not occur. Such turbulences will 
result in increased pressure losses and 
in acoustic noise in the pipe system. In 
addition to drawn copper piping a pipe 
system usually comprises 4 elbows, a 
non-return valve, a cut-off valve and an 

external oil ilter.

The sum of these individual resistances 

is  so  insigniicant  that  they  can  be 

disregarded. The tables do not 
include any lengths exceeding 100 m 
as experience shows that longer lengths 
are not needed.
The tables apply to a standard fuel oil of 
normal commercial quality according 
to current standards. On commis sioning 
with an empty tube system the oil 
pump should not be run without oil for 
more than 5 min. (a condition is that 
the pump is being lubricated during 
operation).
The tables state the total suction line 
length in metres at a nozzle capacit of 

10,0 kg/h. Max. permissible pressure

 

at the suction and pressure side is 
2,0 bar.

Purging

On 1-pipe systems it is necessary to 
purge the pump. On 2-pipe systems 
purging is automatic through the 
return line.

171 505 09  10-01

Two-pipe system
 Height 

 

Pipe  diameter 

 

  H 

ø6 mm  ø8 mm  ø10 mm

 

m m m m

 0 

11 

34 

84

 -0,5 

10 

30 

74

 -1,0 

26 

64

 -1,5 

22 

54

 -2,0 

18 

44

 -2,5 

14 

34

 -3,0 

10 

24

 -3,5 

14

 4,0 

4

 Height 

 

Pipe  diameter

  H 

ø4 mm  ø5 mm  ø6 mm

 

m m m m 

 Height 

 

Pipe  diameter

  H 

ø6 mm  ø8 mm  ø10 mm

 

m m m m

 4,0 

21 

67 

100

 3,5 

20 

63 

100

 3,0 

19 

59 

100

 2,5 

17 

55 

100

 2,0 

16 

51 

100

 1,5 

15 

46 

100

 1,0 

13 

42 

100

 0,5 

12 

38 

94

 Height 

 

Pipe  diameter

  H 

ø5 mm  ø6 mm  ø8 mm

 

m m m m

 4,0 

31 

65 

100

 3,5 

27 

57 

100

 3,0 

23 

49 

100

 2,5 

20 

40 

100

 2,0 

16 

32 

100

 1,5 

12 

24 

77

 1,0 

16 

51

 0,5 

26

1-pipe system

1-pipe system

With an underlying tank a 1-pipe-

system is not recommended

Two-pipe system

H

H

Содержание Bentone B40 CN

Страница 1: ...Providing sustainable energy solutions worldwide 178 032 53 2 2016 07 08 Installation and maintenance instruction B40 CN...

Страница 2: ......

Страница 3: ...y 5 Ignition cable 6 Ignition transformer 7 Photo cell 8 Control box 9 Reset button 10 Cover inspection glass 11 Fan wheel 12 Motor 13 Nozzle assembly adjustment 14 Blast tube 15 Air adjustment 16 Air...

Страница 4: ...deinite spray angle or spray pattern Recommended nozzle Output range and nozzles recommended The net caloriic value of 11 86 kWh kg for light oil has been used Burner tube Length of burner tube Measu...

Страница 5: ...s fol lows Increase the nozzle assembly adjustment somewhat The CO2 con tent and consequently the air volume will then be reduced GENERAL INSTRUCTIONS Condensation in chimney A modern burner works wit...

Страница 6: ...ch off power at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A Service of burner head 1 Loosenorswingouttheburner from the boiler 2...

Страница 7: ...l burner control A2 Twin thermostat F1 Fuse max 10A H1 Alarm lamp H2 Signal lamp optional M1 Burner motor P1 Time meter optional R1 Photoresistor S3 Main switch T1 Ignition transformer Y1 Solenoid val...

Страница 8: ...e burner will make an attempt to re start 3 4 Operating position If the burner operation is interrupted by means of the main switch or the thermostat a new start takes place when the conditions in acc...

Страница 9: ...blesapplytoastandardfueloilof normal commercial quality according tocurrentstandards Oncommissioning with an empty tube system the oil pump should not be run without oil for more than 5 min a conditio...

Страница 10: ...f the pump is overloaded i e If you try to get out more oil than the gear setcansupplyunderexistingcircum stances the oilpressurefallsbelowthe setvalue andthevalveclosesagainst 171 505 10 10 01 Replac...

Страница 11: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Страница 12: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Страница 13: ...f magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocel...

Страница 14: ......

Страница 15: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: