03. INSTALLATION

Acceptance inspection

Ensure that everything is delivered and that there is no transport damage.
If there is anything wrong with the delivery, please report it to the supplier.
Any transport damage should be reported to the forwarding company.

Preparations for installation

Ensure that the size and capacity range of the burner are suitable for the
boiler. Power data on the data plate refer to the minimum and maximum
power of the burner.

Distribution of oil

To ensure satisfactory operation it is essential that the oil distribution sys-
tem is correct.
Observe the following:
- See Pump instructions for choice of tube diameter, tube length and height

difference.

- Fix the tubing with a minimum number of screw fittings.
- Fix the tubes so that the oil hoses are not subjected to tensile stress or

sharp bending when swinging out the burner or removing it for service.

- Fit the oil filter so that the filter cartridge can easily be replaced, see Oil

filter Bentone.

Electrical connections

The main power switch must be turned off before beginning the electrical
installation. If the boiler has a 7-pole contact device type Eurostecker it will
most often fit the burner direct. Otherwise use the accompanying contact
device. The operating thermostat and maximum thermostat, and also any
fire-door switch, can then be connected in series with the incoming phase
or be connected between T1 and T2. In the first case T1 and T2 are to be
strapped.

If another electrical connection is used than the one recommended  by
Bentone, there might be a risk of material damage or personal injury.

Choice of nozzle

See under Technical Data: Recommended nozzle and table of nozzles.

Setting of the shrouded disc and air flow

The burner is pre-set on delivery in relation to the nozzle provided. If the
size of the nozzle is changed the burner can be initially set according to
“Basic settings”. Note that it is only a question of a basic setting that
should be trimmed when the burner is started. This should include a flue
gas analysis and measurement of soot.

V

!

Warning

Содержание Bentone B2S Classic

Страница 1: ...Providing sustainable energy solutions worldwide 178 017 32 Installation and maintenance instruction B2S Classic...

Страница 2: ......

Страница 3: ...t of the shrouded disc 10 05 MAINTENANCE 11 Suspension of burner 11 Removing the blast tube 11 Setting the ignition electrodes 11 Cleaning the fan wheel 12 Trimming 12 Automatic air damper 12 Service...

Страница 4: ......

Страница 5: ...ontact X1 X2 see wiring diagram 5 Air damper 6 Oil pipe 7 Electrodes 8 Fan housing 9 Adjustment of nozzle assembly 10 Frame 11 Control box 12 Blast tube 13 Oil pump 14 Ignition transformer 15 Motor 16...

Страница 6: ...n CE suivantes 2004 108 EC Elektromagnetisk kompatibilitet Electromagnetic compatibility EC Richtlinie Compatibilit lectromagn tique 2006 95 EC L gsp nningsdirektivet Low voltage directive Niederspann...

Страница 7: ...nal way so that the risk of leaking oil fire or personal injury is avoided Care should be taken by the installer to ensure that no electrical cables or fuel gas pipes are trapped or damaged during ins...

Страница 8: ...3 22 38 2 0 85 2 96 35 1 3 14 37 2 3 31 39 2 3 47 41 1 3 63 43 0 1 00 3 33 39 4 3 53 41 8 3 72 44 1 3 90 46 2 4 08 48 3 1 10 3 79 44 9 4 02 47 7 4 24 50 2 4 45 52 7 4 64 55 0 1 20 3 98 47 2 4 22 50 0...

Страница 9: ...artridge can easily be replaced see Oil filter Bentone Electrical connections The main power switch must be turned off before beginning the electrical installation If the boiler has a 7 pole contact d...

Страница 10: ...disc Pump pressure bar Nozzle assembly scale Air scale Fan pressure mbar Burner output kW Burner output kW 9 2 5 6 10 8 7 4 3 1 0 70 80 100 60 90 50 40 30 Burner output kW 70 80 100 60 90 50 40 30 2...

Страница 11: ...ews one turn 2 Turn to the right and withdraw the blast tube Setting the ignition electrodes Proper setting of the electrodes is essential to ensure satisfactory opera tion of the burner If the spark...

Страница 12: ...e assembly until a soot coefficient 0 5 1 is achieved increasetheairtogiveasafetymarginof0 5 1 CO2 beforesootiscreated To throttle more with the shrouded disc smaller reading on the nozzle assembly sc...

Страница 13: ...age Loosen the hexagon nut from the stud bolt Pull the electric package backwards and rotate it ca 90 clockwise When required the electric package can be suspended in the cables Pump filter When chang...

Страница 14: ...Venting Venting is only necessary in a one pipe system In two pipe systems the pump is automatically vented by the return pipe Changing cartridge filter Unscrew the filter screw from the cover using a...

Страница 15: ...d by the pressure set on the control valve P1 and by the size of the oil nozzle in the nozzle line The control valve P1 operates as follows When the oil attains opening pressure the port to the return...

Страница 16: ...sum of these individual resistances is negligible The tables do not include any lengths exceeding 100 m because experience shows that longer lengths are not needed The tables apply to standard fuel oi...

Страница 17: ...ilter cartridge A yearly B when the vacuum becomes 0 4 bar greater during operation than when still C when the entire filter appears to be dirty Remember to remove the flat gasket between the cartridg...

Страница 18: ...18 171 855 18 04 01 09 ELECTRICAL EQUIPMENT LOA24 Wiring diagram 1 2 1 2...

Страница 19: ...this time limit the burner will make an attempt to re start 3 4 Operating position If the burner operation is interrupted by means of the main switch or the thermostat a new start takes place when th...

Страница 20: ...lay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue draught is preventing flame establishment No spark Check that...

Страница 21: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 22: ......

Страница 23: ......

Страница 24: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: