09. ELECTRICAL EQUIPMENT LOA24...

List of components

A1

Oil burner control

R1

Photoresistor

A2

Twin thermostat

S3

Main switch

F1

Fuse, max. 10A

T1

Ignition transformer

H1

Alarm lamp

Y1

Solenoid valve

H2

Signal lamp (optional)

X1

Plug-in contact, burner

M1 Burner motor

X2

Plug-in contact, boiler

P1

Time meter (optional)

Mains connection and fuses in accor-dance with local regulations.

Function

1. Switch on operating switch and twin thermostat

The burner motor starts, an ignition spark is formed, the prepurge goes
on till the prepurge period expires and the solenoid valve opens (2).

2. Solenoid valve opens

Oil mist is formed and ignited. The photocell indicates a flame.

(1)

The ignition spark goes out 15 s. after flame indication 

(LOA24.171...)

.

(2)

The ignition spark goes out 2 s. after flame indication when the ignition
transformer is connected to terminal 7

 (LOA24.173...)

.

3. The safety time expires

a.

If no flame is established before this time limit the control cuts out.

b.

If for some reasons the flame disappears after this time limit, the
burner will make an attempt to re-start.

3-4. Operating position

If the burner operation is interrupted by means of the main switch or the
thermostat, a new start takes place when the conditions in accordance
with point 1 are fulfilled.

The oil burner control cuts out

A red lamp in the control is lit. Press the reset button and the burner
re-starts.

Post-ignition
(2)

If a post-igniton of 15 s. is wanted, move the ignition transformer from
terminal 7 to terminal 6 

(LOA24.173...)

.

Technical data

Pre-ignition time:

13 s

Pre-purge time:

13 s

(1)

 Post-ignition time:

15 s

(2)

 Post-ignition time:

2 s

Safety lock-out time:

10 s

Reset time after lockout:

» 50 s

Reaction time on flame failure:

max.  1  s

Ambient temperature:

from - 20 to +60°C

Min. current with flame established:

65 µ A

Max. photo current at start:

5 µ A

Enclosure:

IP 40

(Under voltage proof only LOA24...)

Control of photo current

Current through photo unit is measured with a d.c. ammeter (a moving coil
instrument connected in series with the photo unit).

Outer electrical connection

* If there is no plug-in contact (X2) on

the boiler, connect to the contact
enclosed. In case the twin thermo-
stat is in series on incoming phase
L1, a loop between the terminals
T1 and T2 is necessary.

X1

X2

Содержание Bentone B2S Classic

Страница 1: ...Providing sustainable energy solutions worldwide 178 017 32 Installation and maintenance instruction B2S Classic...

Страница 2: ......

Страница 3: ...t of the shrouded disc 10 05 MAINTENANCE 11 Suspension of burner 11 Removing the blast tube 11 Setting the ignition electrodes 11 Cleaning the fan wheel 12 Trimming 12 Automatic air damper 12 Service...

Страница 4: ......

Страница 5: ...ontact X1 X2 see wiring diagram 5 Air damper 6 Oil pipe 7 Electrodes 8 Fan housing 9 Adjustment of nozzle assembly 10 Frame 11 Control box 12 Blast tube 13 Oil pump 14 Ignition transformer 15 Motor 16...

Страница 6: ...n CE suivantes 2004 108 EC Elektromagnetisk kompatibilitet Electromagnetic compatibility EC Richtlinie Compatibilit lectromagn tique 2006 95 EC L gsp nningsdirektivet Low voltage directive Niederspann...

Страница 7: ...nal way so that the risk of leaking oil fire or personal injury is avoided Care should be taken by the installer to ensure that no electrical cables or fuel gas pipes are trapped or damaged during ins...

Страница 8: ...3 22 38 2 0 85 2 96 35 1 3 14 37 2 3 31 39 2 3 47 41 1 3 63 43 0 1 00 3 33 39 4 3 53 41 8 3 72 44 1 3 90 46 2 4 08 48 3 1 10 3 79 44 9 4 02 47 7 4 24 50 2 4 45 52 7 4 64 55 0 1 20 3 98 47 2 4 22 50 0...

Страница 9: ...artridge can easily be replaced see Oil filter Bentone Electrical connections The main power switch must be turned off before beginning the electrical installation If the boiler has a 7 pole contact d...

Страница 10: ...disc Pump pressure bar Nozzle assembly scale Air scale Fan pressure mbar Burner output kW Burner output kW 9 2 5 6 10 8 7 4 3 1 0 70 80 100 60 90 50 40 30 Burner output kW 70 80 100 60 90 50 40 30 2...

Страница 11: ...ews one turn 2 Turn to the right and withdraw the blast tube Setting the ignition electrodes Proper setting of the electrodes is essential to ensure satisfactory opera tion of the burner If the spark...

Страница 12: ...e assembly until a soot coefficient 0 5 1 is achieved increasetheairtogiveasafetymarginof0 5 1 CO2 beforesootiscreated To throttle more with the shrouded disc smaller reading on the nozzle assembly sc...

Страница 13: ...age Loosen the hexagon nut from the stud bolt Pull the electric package backwards and rotate it ca 90 clockwise When required the electric package can be suspended in the cables Pump filter When chang...

Страница 14: ...Venting Venting is only necessary in a one pipe system In two pipe systems the pump is automatically vented by the return pipe Changing cartridge filter Unscrew the filter screw from the cover using a...

Страница 15: ...d by the pressure set on the control valve P1 and by the size of the oil nozzle in the nozzle line The control valve P1 operates as follows When the oil attains opening pressure the port to the return...

Страница 16: ...sum of these individual resistances is negligible The tables do not include any lengths exceeding 100 m because experience shows that longer lengths are not needed The tables apply to standard fuel oi...

Страница 17: ...ilter cartridge A yearly B when the vacuum becomes 0 4 bar greater during operation than when still C when the entire filter appears to be dirty Remember to remove the flat gasket between the cartridg...

Страница 18: ...18 171 855 18 04 01 09 ELECTRICAL EQUIPMENT LOA24 Wiring diagram 1 2 1 2...

Страница 19: ...this time limit the burner will make an attempt to re start 3 4 Operating position If the burner operation is interrupted by means of the main switch or the thermostat a new start takes place when th...

Страница 20: ...lay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue draught is preventing flame establishment No spark Check that...

Страница 21: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 22: ......

Страница 23: ......

Страница 24: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: