13
IOM, BS/BT Models
Enertech Global
A Coil Dimensional and Physical Data
A
C
B
⚠
WARNING
⚠
IF USING A DUAL FUEL
APPLICATION, “A” COIL MUST BE
INSTALLED ON THE OUTLET OF
THE FURNACE. INSTALLATION
ON THE RETURN COULD CAUSE
FURNACE HEAT EXCHANGER
FAILURE, AND MAY VOID
FURNACE WARRANTY.
NOTES:
1
. The AC series coils are designed as high efficiency “A” coils to be
installed on new and existing indoor furnaces. These coils may be used
in up flow and down flow applications.
2. Coils are ETL and CSA approved.
3. Primary and secondary drain connections are available on the LH or RH
side of the drain pan, and are 3/4” FPT. Center line of drains located
from pan corner, 1 1/2” for primary and 3 1/2” for secondary.
4. Drain pan is injection molded high temperature UL approved plastic.
5. All coils are equipped with factory-installed TXV, 15% bleed type.
Model
Size
(tons)
All Dimensions in Inches
A
B
C
Liquid
Suction
ACD024B
2
16 5/8
19
14 1/2
3/8
3/4
ACD036B
3
19 5/8
19
18 1/2
3/8
3/4
ACD060C
4 - 6
23 3/4
20 1/2
27 7/8
3/8
7/8
Model
Size
(Tons)
All Dimensions In Inches (nominal)
Weight
(lbs...)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
024
2
17.5
21.0
20.0
15.2
19.2
2.1
4.1 1.8
2.3
11.1
8.5
13.8 9.2
11.0
3.3 .88
.38
45
036
3
21.0
21.0
24.0
18.7
19.2
2.2
4.3 1.8
2.3
12.9
10.6 15.7 11.9
14.2
3.3 .88
.38
50
060
5
24.5
22.0
34.0
22.0
19.9
2.2
4.2 1.9
2.3
17.3
12.8 19.8 24.8
26.8
3.3 .88
.38
72
Section 4: Equipment Data