background image

DELIVERY AND STORAGE

Inspect  for  signs  of  damage  or  missing
components.

Store the battery in a dry, clean and prefe-
rably  cool  and  frost-free  location.  Do  not
expose the cells to direct sunlight as dama-
ge to the container and cover may occur.

As the batteries are supplied charged, sto-
rage time is limited. In order to easily char-
ge the batteries after prolonged storage, it
is advised not to store it more than

6 months at 20°C

4 months at 30°C

2 months at 40°C

A  refreshing  charge  shall  be  performed
after this time or if the open circuit voltage
is below 2.07 Vpc.

Failure  to  observe  these  conditions  may
result in greatly reduced capacity and ser-
vice life.

The refreshing charge shall be carried out
according  to  clause  a)  of  the  commissio-
ning charge paragraph below. Alternatively
the cells can be float-charged at 2.25 Vpc
during storage.

INSTALLATION

The electrical protective measures and the
accommodation and ventilation of the bat-
tery installation must be in accordance with
the  applicable  rules  and  regulations.
Specifically EN 50272-2 applies.

The battery should be installed in a clean,
dry area. It will not emit corrosive gases in

normal  operation  and  can  be  installed
together with other electrical equipment. 

Under normal conditions the gas release is
negligible  and  natural  ventilation  is  suffi-
cient for cooling purposes and inadvertent
overcharge, enabling OPzV batteries to be
used safely in offices or within equipment.
However  care  must  be  taken  to  ensure
adequate  ventilation  when  placed  in 
cabinets. They must not be placed in sealed
cabinets  without  ventilation  openings  at
the  top  and  bottom.Avoid  placing  the 
battery  in  a  warm  place  or  in  direct  sun-
light.  Approved  battery  racks  are  recom-
mended  for  proper  installation.  Place  the
cells on the rack and arrange the positive
and the negative terminals for connection
according the wiring diagram. 

Horizontal Installation

Do not install the cells in such a way that
the box-lid bond is resting on a runner.

Ensure that the internal plates are vertical.

Check that all contact surfaces are clean. If
required clean with a brass brush. Tighten
the terminal screws, taking care to use the
correct  torque  loading  (Tab.  1).  To  avoid
damage to the plastic materials, do not use
grease. Fit the covers supplied for protec-
tion against inadvertent contact. 

Tab. 1: Torque loadings for terminal screws

Type    Terminal screw

Torque

OPzV

M10 

23 – 25 Nm

Carefully  follow  the  polarity  sequence  to
avoid short circuiting cell groups. A loose
connector can make adjusting the charger
difficult,  create  erratic  performance  and
possible  damage  to  the  battery  and/or
even personal injury. Finally, with the char-
ger switched off, the battery fuses remo-
ved  and  the  load  disconnected,  connect
the battery to the D.C. power supply.

Ensure that the polarity is correct - positi-
ve terminal of the battery to the positive
terminal  of  the  charger.  Switch  on  the
charger and charge according to the com-
missioning  charge  paragraph  below.  The
first charge must be monitored to ensure
that the limits are not exceeded and that
no unacceptable temperatures occur. 

Cells  or  monoblocs  in  parallel  strings

OPzV cells monoblocs may be connected
in  parallel  to  give  higher  current 
capability. In the case of parallel connec-
ted  strings,  use  batteries  of  the  same
capacity, design and age only with a maxi-
mum  of  4  parallel  strings.  The  resistance
of  the  cables  in  each  string  must  be  the
same,  e.g.  same  cross-section,  same
length.  Connect  the  battery  strings  in
parallel at the charger terminals.

Handling

OPzV batteries are supplied in a fully charged
state and must be unpacked carefully to avoid
short-circuit between terminals of opposite 
polarity. The cells are heavy and must be lifted
with appropriate equipment.

Keep Flames Away

In the case of an accidental overcharge, a flam-
mable gas may be emitted from the safety valve.
Discharge any possible static electricity 
from clothes by touching an earth-connected
part.

Tools

Use tools with insulated handles.
Do not place or drop metal objects onto the 
battery. Remove rings, wristwatch and metal arti-
cles of clothing that might come into contact
with the battery terminals.

Warranty

Any of the following actions will invalidate the warrranty - Non-adherence to the Installation, Operating and Maintenance instructions. 
Repairs carried out with non-approved spare parts. Application of additives to the electrolyte. Unauthorised interference with the battery. 

PowerSafe OPzV 

Installation, operating 
and maintenance instructions

E

N

G

L

IS

H

No  smoking  no  naked
flames, no sparks

Electrical hazard

Electrolyte is corrosive, 
in case of broken
containers/lids 

Shield eyes

Danger

Clean all acid splash in eyes or
on skin with lot of clear water. 
Then visit a doctor.
Acid on clothing is to be washed
with water.

+

Note operating
instructions

Recycle scrap 
batteries. 
Contains lead

Warning: Risk of fire, explosion, or
burns. Do not disassemble, heat
above 60ºC, or incinerate. Avoid
any short circuit. Metallic parts

under voltage on the battery, do not place tools
or items on top of the battery

DELIVERY AND STORAGE

Inspect  for  signs  of  damage  or  missing
components.
Store  the  battery  in  a  dry,  clean  and
preferably cool and frost-free location. Do not
expose the cells to direct sunlight as damage
to the container and cover may occur. As the
batteries are supplied charged, storage time is
limited. In order to easily charge the batteries
after  prolonged  storage,  it  is  advised  not  to
store it more than
6 months at 20°C
4 months at 30°C
2 months at 40°C
A  refreshing  charge  shall  be  performed  after
this time or if the open circuit voltage is below
2.07 Vpc.
Failure to observe these conditions may result
in greatly reduced capacity and service life.
The  refreshing  charge  shall  be  carried  out
according  to  clause  a)  of  the  commissioning
charge paragraph below. Alternatively the cells
can  be  float-charged  at  2.25  Vpc  during
storage.

INSTALLATION

The  electrical  protective  measures  and  the
accommodation  and  ventilation  of  the
battery installation must be in accordance with
the  applicable  rules  and  regulations.
Specifically EN 50272-2 applies.
Do  not  use  terminal  posts  to  lift  or  handle
cells.
The battery should be installed in a clean, dry
area. It will not emit corrosive gases in normal
operation  and  can  be  installed  together  with
other  electrical  equipment.  Under  normal
conditions  the  gas  release  is  negligible  and
natural  ventilation  is  sufficient  for  cooling

purposes  and  inadvertent  overcharge,
enabling  OPzV  batteries  to  be  used  safely  in
offices  or  within  equipment.  However  care
must be taken to ensure adequate ventilation
when  placed  in  cabinets.  They  must  not  be
placed  in  sealed  cabinets  without  ventilation
openings at the top and bottom. Avoid placing
the  battery  in  a  warm  place  or  in  direct
sunlight.  Approved  battery  racks  are
recommended  for  proper  installation.  Place
the cells on the rack and arrange the positive
and  the  negative  terminals  for  connection
according the wiring diagram.

Horizontal Installation
Do  not  use  terminal  posts  to  lift  or  handle
cells.
Do not install the cells in such a way that the
box-lid  bond  is  resting  on  a  runner.  Always
ensure that the arrow on the lid of each unit is
pointing in vertical orientation.

Do  not  invert  cells  (vents  upside  down)  or
allow  the  front  of  the  cells  to  be  positioned
lower  than  the  base  of  the  cell  as  it  might
block the safety valve and damage pillars.
Check  that  all  contact  surfaces  are  clean.  If
required clean with a brass brush. Tighten the
terminal screws, taking care to use the correct
torque  loading  (Tab.  1).  To  avoid  damage  to
the plastic materials, do not use grease. Fit the
covers  supplied  for  protection  against
inadvertent contact.

Tab. 1: Torque loadings for terminal screws

Type         Terminal screw       Torque

OPzV              M10             23 – 25 Nm

Carefully follow the polarity sequence to avoid
short circuiting cell groups. A loose connector
can  make  adjusting  the  charger  difficult,
create  erratic  performance  and  possible
damage  to  the  battery  and/or  even  personal
injury.  Finally,  with  the  charger  switched  off,
the  battery  fuses  removed  and  the  load
disconnected, connect the battery to the D.C.
power supply.
Ensure  that  the  polarity  is  correct  -
positive terminal of the battery to the positive
terminal of the charger. Switch on the charger
and  charge  according  to  the  commissioning
charge paragraph below. The first charge must
be monitored to ensure that the limits are not
exceeded  and  that  no  unacceptable
temperatures occur.

Cells or monoblocs in parallel strings
OPzV  cells  monoblocs  may  be  connected  in
parallel to give higher current capability. In the
case  of  parallel  connected  strings,  use
batteries of the same capacity, design and age
only with a maximum of 4 parallel strings. The
resistance of the cables in each string must be
the same, e.g. same cross-section, same length.
Connect  the  battery  strings  in  parallel  at  the
charger terminals

1

Содержание PowerSafe OPzV

Страница 1: ...ion Operations and Maintenance Instructions Consignes d installation d exploitation et de maintenance Gebrauchsanweisung und Bedienungsanleitung Normas de instalaci n utilizaci n y mantenimiento RESER...

Страница 2: ...re parts Application of additives to the electrolyte Unauthorised interference with the battery PowerSafe OPzV Installation operating and maintenance instructions ENGLISH No smoking no naked flames no...

Страница 3: ...UE by not more than 0 2 Vpc A low voltage dis connect is recommended to prevent deep discharge Special attention should be given to small loads that are not automatically dis connected at the end of...

Страница 4: ...e des temp ratures inacceptables Montage des l ments en parall le Les l ments OPzV peuvent tre connect s en parall le pour fournir une capacit plus lev e Pour ce type de montage utiliser uniquement de...

Страница 5: ...harge 1h t 5h 1 70 V lement 5h t 8h 1 75 V lement 8h t 24h 1 80 V lement Les tensions individuelles ne doivent jamais tre inf rieures de plus de 0 2 V l ment par rapport la tension finale Une coupure...

Страница 6: ...ef hrliche Spannung bei Spannungen 60Vdc Elektrolyt ist stark tzend Im normalen Betrieb ist Ber hrung mit dem Elektrolyten ausgeschlossen Bei Zerst rung der Geh use ist der freiwerdende gebundene Elek...

Страница 7: ...ine Entlade str me die am Entladeende nicht automa tisch abgeschaltet werden Entladene Zellen Nach Entladungen auch Teilentladungen sind OPzV Batterien sofort aufzuladen Standzeiten im entladenen Zust...

Страница 8: ...l o a los ojos Consultar a un m dico La ropa con cido debe lavarse con agua Seguir las instrucciones de uso Reciclar los componentes de la bater a Contiene plomo Aviso Riesgo de fuego explosi n o ince...

Страница 9: ...carga debe limitarse a los valores siguientes Duraci n de la descarga Tensi n final 1h t 5h 1 70 V elemento 5h t 8h 1 75 V elemento 8h t 24h 1 80 V elemento Las tensiones individuales no deber n nunca...

Страница 10: ...Notes...

Страница 11: ......

Страница 12: ...teway East Building Level 11 189721 Singapore Tel 65 6508 1780 2013 EnerSys All rights reserved Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted EnerSys EMEA...

Отзывы: