background image

DELIVERY AND STORAGE

Inspect  for  signs  of  damage  or  missing
components.

Store the battery in a dry, clean and prefe-
rably  cool  and  frost-free  location.  Do  not
expose the cells to direct sunlight as dama-
ge to the container and cover may occur.

As the batteries are supplied charged, sto-
rage time is limited. In order to easily char-
ge the batteries after prolonged storage, it
is advised not to store it more than

6 months at 20°C

4 months at 30°C

2 months at 40°C

A  refreshing  charge  shall  be  performed
after this time or if the open circuit voltage
is below 2.07 Vpc.

Failure  to  observe  these  conditions  may
result in greatly reduced capacity and ser-
vice life.

The refreshing charge shall be carried out
according  to  clause  a)  of  the  commissio-
ning charge paragraph below. Alternatively
the cells can be float-charged at 2.25 Vpc
during storage.

INSTALLATION

The electrical protective measures and the
accommodation and ventilation of the bat-
tery installation must be in accordance with
the  applicable  rules  and  regulations.
Specifically EN 50272-2 applies.

The battery should be installed in a clean,
dry area. It will not emit corrosive gases in

normal  operation  and  can  be  installed
together with other electrical equipment. 

Under normal conditions the gas release is
negligible  and  natural  ventilation  is  suffi-
cient for cooling purposes and inadvertent
overcharge, enabling OPzV batteries to be
used safely in offices or within equipment.
However  care  must  be  taken  to  ensure
adequate  ventilation  when  placed  in 
cabinets. They must not be placed in sealed
cabinets  without  ventilation  openings  at
the  top  and  bottom.Avoid  placing  the 
battery  in  a  warm  place  or  in  direct  sun-
light.  Approved  battery  racks  are  recom-
mended  for  proper  installation.  Place  the
cells on the rack and arrange the positive
and the negative terminals for connection
according the wiring diagram. 

Horizontal Installation

Do not install the cells in such a way that
the box-lid bond is resting on a runner.

Ensure that the internal plates are vertical.

Check that all contact surfaces are clean. If
required clean with a brass brush. Tighten
the terminal screws, taking care to use the
correct  torque  loading  (Tab.  1).  To  avoid
damage to the plastic materials, do not use
grease. Fit the covers supplied for protec-
tion against inadvertent contact. 

Tab. 1: Torque loadings for terminal screws

Type    Terminal screw

Torque

OPzV

M10 

23 – 25 Nm

Carefully  follow  the  polarity  sequence  to
avoid short circuiting cell groups. A loose
connector can make adjusting the charger
difficult,  create  erratic  performance  and
possible  damage  to  the  battery  and/or
even personal injury. Finally, with the char-
ger switched off, the battery fuses remo-
ved  and  the  load  disconnected,  connect
the battery to the D.C. power supply.

Ensure that the polarity is correct - positi-
ve terminal of the battery to the positive
terminal  of  the  charger.  Switch  on  the
charger and charge according to the com-
missioning  charge  paragraph  below.  The
first charge must be monitored to ensure
that the limits are not exceeded and that
no unacceptable temperatures occur. 

Cells  or  monoblocs  in  parallel  strings

OPzV cells monoblocs may be connected
in  parallel  to  give  higher  current 
capability. In the case of parallel connec-
ted  strings,  use  batteries  of  the  same
capacity, design and age only with a maxi-
mum  of  4  parallel  strings.  The  resistance
of  the  cables  in  each  string  must  be  the
same,  e.g.  same  cross-section,  same
length.  Connect  the  battery  strings  in
parallel at the charger terminals.

Handling

OPzV batteries are supplied in a fully charged
state and must be unpacked carefully to avoid
short-circuit between terminals of opposite 
polarity. The cells are heavy and must be lifted
with appropriate equipment.

Keep Flames Away

In the case of an accidental overcharge, a flam-
mable gas may be emitted from the safety valve.
Discharge any possible static electricity 
from clothes by touching an earth-connected
part.

Tools

Use tools with insulated handles.
Do not place or drop metal objects onto the 
battery. Remove rings, wristwatch and metal arti-
cles of clothing that might come into contact
with the battery terminals.

Warranty

Any of the following actions will invalidate the warrranty - Non-adherence to the Installation, Operating and Maintenance instructions. 
Repairs carried out with non-approved spare parts. Application of additives to the electrolyte. Unauthorised interference with the battery. 

PowerSafe OPzV 

Installation, operating 
and maintenance instructions

E

N

G

L

IS

H

No  smoking  no  naked
flames, no sparks

Electrical hazard

Electrolyte is corrosive, 
in case of broken
containers/lids 

Shield eyes

Danger

Clean all acid splash in eyes or
on skin with lot of clear water. 
Then visit a doctor.
Acid on clothing is to be washed
with water.

+

Note operating
instructions

Recycle scrap 
batteries. 
Contains lead

Warning: Risk of fire, explosion, or
burns. Do not disassemble, heat
above 60ºC, or incinerate. Avoid
any short circuit. Metallic parts

under voltage on the battery, do not place tools
or items on top of the battery

DELIVERY AND STORAGE

Inspect  for  signs  of  damage  or  missing
components.
Store  the  battery  in  a  dry,  clean  and
preferably  cool  and  frost-free  location.  Do
not  expose  the  cells  to  direct  sunlight  as
damage  to  the  container  and  cover  may
occur. As the batteries are supplied charged,
storage  time  is  limited.  In  order  to  easily
charge the batteries after prolonged storage,
it is advised not to store it more than
12 months at 20°C
6 months at 30°C
3 months at 40°C
A refreshing charge shall be performed after
this  time  or  if  the  open  circuit  voltage  is
below 2.07 Vpc.
Failure  to  observe  these  conditions  may
result in greatly reduced capacity and service
life.
The  refreshing  charge  shall  be  carried  out
according to clause a) of the commissioning
charge  paragraph  below.  Alternatively  the
cells can be float-charged at 2.25 Vpc during
storage.

INSTALLATION

The  electrical  protective  measures  and  the
accommodation  and  ventilation  of  the
battery  installation  must  be  in  accordance
with  the  applicable  rules  and  regulations.
Specifically EN 50272-2 applies.
Do  not  use  terminal  posts  to  lift  or  handle
cells.
The battery should be installed in a clean, dry
area.  It  will  not  emit  corrosive  gases  in
normal  operation  and  can  be  installed
together  with  other  electrical  equipment.
Under  normal  conditions  the  gas  release  is
negligible and natural ventilation is sufficient

for  cooling  purposes  and  inadvertent
overcharge,  enabling  OPzV  batteries  to  be
used  safely  in  offices  or  within  equipment.
However  care  must  be  taken  to  ensure
adequate  ventilation  when  placed  in
cabinets. They must not be placed in sealed
cabinets  without  ventilation  openings  at  the
top and bottom. Avoid placing the battery in
a warm place or in direct sunlight. Approved
battery  racks  are  recommended  for  proper
installation.  Place  the  cells  on  the  rack  and
arrange  the  positive  and  the  negative
terminals for connection according the wiring
diagram.

Horizontal Installation
Do  not  use  terminal  posts  to  lift  or  handle
cells.
Do not install the cells in such a way that the
box-lid  bond  is  resting  on  a  runner.  Always
ensure that the arrow on the lid of each unit
is pointing in vertical orientation.

Do  not  invert  cells  (vents  upside  down)  or
allow  the  front  of  the  cells  to  be  positioned
lower  than  the  base  of  the  cell  as  it  might
block the safety valve and damage pillars.
Check  that  all  contact  surfaces  are  clean.  If
required  clean  with  a  brass  brush.  Tighten
the  terminal  screws,  taking  care  to  use  the
correct  torque  loading  (Tab.  1).  To  avoid
damage to the plastic materials, do not use
grease. Fit the covers supplied for protection
against inadvertent contact.

Tab. 1: Torque loadings for terminal screws

Type         Terminal screw       Torque

OPzV              M10             23 – 25 Nm

Carefully  follow  the  polarity  sequence  to
avoid  short  circuiting  cell  groups.  A  loose
connector  can  make  adjusting  the  charger
difficult,  create  erratic  performance  and
possible damage to the battery and/or even
personal  injury.  Finally,  with  the  charger
switched off, the battery fuses removed and
the  load  disconnected,  connect  the  battery
to the D.C. power supply.
Ensure  that  the  polarity  is  correct  -
positive terminal of the battery to the positive
terminal  of  the  charger.  Switch  on  the
charger  and  charge  according  to  the
commissioning charge paragraph below. The
first charge must be monitored to ensure that
the  limits  are  not  exceeded  and  that  no
unacceptable temperatures occur.

Cells or monoblocs in parallel strings
OPzV cells monoblocs may be connected in
parallel  to  give  higher  current  capability.  In
the  case  of  parallel  connected  strings,  use
batteries  of  the  same  capacity,  design  and
age  only  with  a  maximum  of  4  parallel
strings. The resistance of the cables in each
string  must  be  the  same,  e.g.  same  cross-
section,  same  length.  Connect  the  battery
strings in parallel at the charger terminals

1

Содержание PowerSafe OPzV Series

Страница 1: ...tion Operations and Maintenance Instructions Consignes d installation d exploitation et de maintenance Gebrauchsanweisung und Bedienungsanleitung Normas de instalación utilización y mantenimiento RESERVE POWER ...

Страница 2: ...are parts Application of additives to the electrolyte Unauthorised interference with the battery PowerSafe OPzV Installation operating and maintenance instructions ENGLISH No smoking no naked flames no sparks Electrical hazard Electrolyte is corrosive in case of broken containers lids Shield eyes Danger Clean all acid splash in eyes or on skin with lot of clear water Then visit a doctor Acid on cl...

Страница 3: ...ow UE by not more than 0 2 Vpc A low voltage dis connect is recommended to prevent deep discharge Special attention should be given to small loads that are not automatically dis connected at the end of discharge Discharged Cells and monoblocs OPzV batteries must not be left in a discharged condition after supplying the load but must be immediately returned to recharge mode Failure to observe these...

Страница 4: ... INSTALLATION Les mesures de protection électrique l emplacement et la ventilation de l installation de la batterie doivent être conformes aux normes et réglements en vigueur La norme EN 50272 2 s applique tout particulièrement Ne pas soulever ou manipuler les éléments par les bornes La batterie doit être installée dans un endroit sec et propre Ne dégageant pas de gaz corrosif en fonctionnement no...

Страница 5: ...ous Durée décharge 1h t 5h 1 70 V élement 5h t 8h 1 75 V élement 8h t 24h 1 80 V élement Les tensions individuelles ne doivent jamais être inférieures de plus de 0 2 V élément par rapport à la tension finale Une coupure à faible tension est recommandée pour éviter la décharge profonde Faire attention aux petits équipements qui ne sont pas automati quement déconnectés à la fin de la décharge Elémen...

Страница 6: ...hr Gefährliche Spannung bei Spannungen 60Vdc Elektrolyt ist stark ätzend Im normalen Betrieb ist Berührung mit dem Elektrolyten ausgeschlossen Bei Zerstörung der Gehäuse ist der freiwerdende gebundene Elektrolyt genauso ätzend wie flüssiger Bei Arbeiten an Batterien Schutzbrille und Schutz kleidung tragen Unfallverhütungsvorschriften beachten Vorsicht Blockbatterien Zellen haben großes Gewicht Auf...

Страница 7: ...ine Entlade ströme die am Entladeende nicht automa tisch abgeschaltet werden Entladene Zellen Nach Entladungen auch Teilentladungen sind OPzV Batterien sofort aufzuladen Standzeiten im entladenen Zustand führen zu erheblich reduzierter Gebrauchsdauer und Zuverlässigkeit Tiefentladung Ist eine Batterie irrtümlich tiefentladen worden ist zuerst mit 2 25 V Zelle zu laden anschließend muß eine im Kapi...

Страница 8: ...iel o a los ojos Consultar a un médico La ropa con ácido debe lavarse con agua Seguir las instrucciones de uso Reciclar los componentes de la batería Contiene plomo Aviso Riesgo de fuego explosión o incendio No se debe desmontar ni calentar por encima de 60ºC ni incinerar Evitar cortocircuitos ESPAÑOL 7 Garantía El no respetar las normas de instalación utilización y mantenimiento reparaciones llev...

Страница 9: ...ón de la descarga Tensión final 1h t 5h 1 70 V elemento 5h t 8h 1 75 V elemento 8h t 24h 1 80 V elemento Las tensiones individuales no deberán nunca ser inferiores en más de 0 2 V elemento respecto a la tensión final Se recomienda aplicar un equipo de control de tensión mínima para evitar la descarga profunda Prestar atención a los pequeños equipos que no se desconectan automáticamente al final de...

Страница 10: ...Notes ...

Страница 11: ......

Страница 12: ...d Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted EnerSys 2366 Bernville Road Reading PA 19605 USA Tel 1 610 208 1991 1 800 538 3627 Fax 1 610 372 8613 EnerSys Asia 152 Beach Road Gateway East Building Level 11 189721 Singapore Tel 65 6508 1780 EnerSys EMEA EH Europe GmbH Baarerstrasse 18 6300 Zug Switzerland ...

Отзывы: