15°C
20°C
25°C
35°C
45°C
1.147
1.144
1.142
1.138
1.131
1.167
1.164
1.162
1.157
1.149
1.186
1.183
1.180
1.176
1.168
1.206
1.203
1.200
1.194
1.187
1.217
1.213
1.210
1.204
1.197
1.227
1.223
1.220
1.214
1.207
1.237
1.233
1.230
1.224
1.216
1.244
1.240
1.237
1.231
1.223
1.248
1.244
1.241
1.234
1.226
1.254
1.250
1.247
1.240
1.232
1.259
1.255
1.252
1.245
1.236
1.270
1.266
1.263
1.256
1.247
Specific gravity
8
Measure the specific gravity with a hydrometer.
After reading, squirt the solution back into the cell from which it was drawn.
The nominal specific gravity at the end of the charge at the specified level is for a temperature of 20°C.
If the temperature is above or below 20°C, the specific gravity reading must be adjusted using the table below.
Temperature correction
The specific gravity
(20
º
C) of each cell at the end of the charge should be between 1.235 and 1.240 (maximum level).
5.
Specific gravity reading
Final specific gravity after charging
Example:
If at the end of charge, the specific gravity of the electrolyte reads 1.231 at 35
º
C, this is equivalent to a specific gravity of
1.240 at 20
º
C. This means that the cell is fully charged.