background image

Publication No: EN-HX+-IOM-00

2

 - 

October

 

201

8

 - Subject to revisions without prior notice. E.&O.E.

EnerSys Asia

 

152 Beach Road 

Gateway East Building #11-03 

Singapore 189721 

Tel: +65 6508 1780

EnerSys World Headquarters

 

2366 Bernville Road, Reading 

PA 19605, USA  

Tel: +1-610-208-1991 / 

+1-800-538-3627

EnerSys EMEA

 

EH Europe GmbH 

Baarerstrasse 18 

6300 Zug, Switzerland  

© 201

8

 EnerSys. All rights reserved. Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted.

Contact

• Every six months (record all readings)
- Measure the battery string voltage. If necessary, adjust the float

voltage to the correct value.

- Measure individual bloc

 

voltages.

-

Bloc

 to 

bloc 

connection resistance (Ohms)

- Terminal Connection Resistance (Ohms)

- Ambient temperature in the immediate environment

Inspect for contamination by dust, lose or corroded connections. If 

necessary, isolate the string/bloc and clean with a damp soft cloth. 

Warning: Do NOT use any type of oil, solvent, detergent, 

petroleum-based solvent or ammonia solution to clean the battery 

containers or lids. These materials will cause permanent damage to 

the battery container and lid and will invalidate the warranty.

Keep a logbook to record values, power outages, discharge tests, 

etc.

An autonomy check can be carried out once or twice a year.

The above record taking is the absolute minimum to protect the 

warranty.

This data will be required for any warranty claim made on the 

battery.

Contact EnerSys

®

 if you have any questions regarding 

maintenance.

7. Disposal

DataSafe

®

 HX+ batteries are recyclable. Scrap batteries must 

be packaged and transported in accordance with prevailing 

transportation rules and regulations.

Scrap batteries must be disposed of in compliance with local and 

national laws by a licensed or certified lead acid battery.