background image

3

3.

 

Battery Location

The battery compartment/room must have adequate ventilation 

to limit hydrogen accumulation. Batteries must be installed in 

accordance with 

prevailing standards

 and any other local/national 

laws and regulations.

4.

 

Installation

Install in a clean and dry area. DataSafe

®

 HX+ batteries 

release minimal amounts of gas during normal operation (gas 

recombination efficiency 

 95%). They can be installed near the 

main equipment. Batteries must be installed in accordance with 

local, national and international regulations and manufacturer’s 

instructions.

Temperature

Avoid placing the battery in areas of high temperature or in direct 

sunlight.  The battery will give the best performance and service 

life when working at a temperature between 20°C and 25°C. The 

maximum operating temperature range is -30°C to +45°C.

Ventilation

Under normal conditions gas release is very low and natural 

ventilation is sufficient for cooling purposes and inadvertent 
overcharge, enabling DataSafe HX+ batteries to be used safely in 

offices and with main equipment.

However care must be taken to ensure adequate ventilation when 

placed in cabinets. Batteries must not be placed in sealed cabinets.

Security

All installation and ventilation must comply with the current local, 

national and international regulations.

Mounting

Batteryracksorcabinets,suppliedbyEnerSys,

are recommended 

for proper installation.  Assemble the rack according to 

instructions. Place the monoblocs or cells on the rack and arrange 

the positive and the negative terminals for connection according 

to the wiring diagram. Check that all contact surfaces are clean 

and apply the bloc or cell connectors and the terminal screws. 

Tighten the screws securely. Follow the polarity to avoid short 

circuiting of cell groups. Finally connect the battery terminals. It is 

important that the battery is mounted firmly.

Installation of High Voltage Batteries

A battery consisting of 

1

0 or more 

blocs

 connected in series 

presents additional hazards and the following notes on installation 

should be employed.

• During installation process, limit the battery voltage by omitting

inter-cell connectors to give a maximum section voltage of 120V

or 

10 blocs

.

• The omitted inter-cell connectors should be chosen such that

they are in an easily accessible position. These connectors

should only be fitted with the load and charger isolated and

when the rest of the installation is complete.

• Never work alone on high voltage batteries.

• Always use insulated tools and wear approved high voltage

insulating gloves.

• When supplied, fit the “high voltage battery” warning labels in a

prominent position.

Torque

Tighten the nuts or bolts to the recommended levels of fastening 

torque indicated on the product label (if applicable). A loose 

connector can cause problems in charger adjustment, erratic 

battery performance, possible damage to the battery, and/or 

personal injury.

Blocs

 in Parallel Strings

When using constant voltage chargers, ensure that the connections 

between the charger and the end of each string within the battery 

have the same electrical resistance. Parallel strings should be 

limited to five strings except with an expressed written consent 

from EnerSys. Parallel strings of five or more require a battery 

monitoring system that records both voltage and current by string.

5. Operation

5.1. Float Voltage
Constant voltage chargers are recommended. The charging voltage 

should be set at the equivalent of 2.29Vpc at 20°C/68°F or 2.27Vpc 

at 25°C/77°F. The minimum charging voltage, at any temperature, 

is 2.21Vpc. The recommended float voltage temperature 

compensation is as follows:

Temperature (°C/°F)

Due to the phenomena of gas recombination, it is not uncommon 

to note a variation in individual block float voltages of 2% (or up to 

5% for relatively new batteries). However the total voltage of the 

battery shall be within the limits stated above.

5.2. Charging Current

Utilising a constant voltage charger results in a charging current 

that is self limiting. The minimum rectifier current available should 

be the load plus 0.1C

10

 Amps.

5.3. Fast Recharge

Occasionally (4 to 5 times per year) the battery may be recharged 

at 2.40Vpc at 20°C, with the rectifier current limit set to a minimum 

of 0.1C

10

 A. Fast charge should be stopped and reverted to float 

voltage after approximatly 10 to 15 hours.

5.4. Periodic Boost Charge

In normal operation a periodic boost charge is not required. 

However, in some cases such as when extended or repeated line 

power outages result in the battery exeriencing extended periods of 

undercharging, a boost charge equivalent to 2.40Vpc at 20°C for a 

maximum of 15 hours can be applied.

5.5 Ripple Current

Unaccepatble levels of ripple current from the charger or the load 

can cause permanent damage and a reduction in service life.  It is 

recommended to limit the continuous ripple current to 0.05C10A.

5.6 Discharging

For maximum battery life, the end of discharge voltage should 

be limited to 1.60Vpc. Failure to protect batteries from discharges 

exceeding this level may impact the warranty.
In order to protect the battery it is advisable to have system 

monitoring and low voltage cut-out. Deep discharge will produce a 

premature deterioration of the battery and a noticeable reduction in 

the life expectancy of the battery.

Discharged

 

Monoblocs

DataSafe HX+ batteries must not be left in a discharged condition 

after supplying the load, but must be immediately returned to float 

recharge mode. Failure to observe these conditions may result in 

greatly reduced service life and unreliability.

Accidental Deep Discharge

When the battery is completely discharged, the sulphuric acid is 

completely absorbed and the remaining electrolyte consists only of 

water. At this point, the sulphation of the plates is at its maximum, 

considerably increasing the cell’s internal resistance.

Important notice: this type of deep discharge will provoke a 

premature deterioration of the battery and a noticeable effect on 

life expectancy.

6. Maintenance and Records

In practice, the user usually specifies the maintenance schedule 

based on site criticality, location and manpower. However, the 

following may be used as a suggested maintenance schedule.

• Monthly (record all readings)
- Measure the battery string voltage. If necessary, adjust the float

voltage to the correct value.

10/50 15/59 20/68 25/77  30/86  35/95 40/104

Recommended 2.33 2.31 2.29 2.27  2.25  2.23  2.21 
Minimum 

2.31 2.29 2.27 2.25  2.23  2.21  2.21

Отзывы: